TROUBLESHOOTING
12-2
SM TELECOM 1-A.0 GB
No.
SYMPTOM
PROBABLE CAUSE
CORRECTIVE ACTION
11
One of the protections is
activated and compressor
is stopped with no
apparent reason.
Control problem or
refrigeration system
problem.
Perform diagnostics to detect
active protection, and take
action accordingly.
12
Compressor motor is noisy
and no suction is present.
Wrong phase order to
compressor.
Check compressor phase
order.
13
Water leakage from indoor
unit.
Indoor unit drainage tube
is blocked.
Check and open drainage
tube.
14
Freezing of outdoor unit in
HEAT Mode and outdoor
unit base is blocked with
ice.
Connect base heater.
15
Unit operates with wrong
fan speeds or wrong
frequency.
Wrong jumper settings.
Perform diagnostics to obtain
unit model or if operating by
EEPROM parameters.
16
Filter LED comes ON after
512 hours of operation
Clogged air-filter
Replace air-filter. Press the
RESET button.
CONTENTS
Summary of Contents for GC 12 LT
Page 13: ...OUTLINE DIMENSIONS 4 3 SM TELECOM 1 A 0 GB 4 5 Outdoor Unit GC 30T LT CONTENTS...
Page 28: ...CONTROL SYSTEM 11 3 SM TELECOM 1 A 0 GB 11 1 4 Main PCB Controller CONTENTS...
Page 70: ...EXPLODED VIEWS SPARE PARTS LISTS 13 6 SM TELECOM 1 A 0 GB 13 6 Outdoor Unit GC 12 LT CONTENTS...
Page 72: ...EXPLODED VIEWS SPARE PARTS LISTS 13 8 SM TELECOM 1 A 0 GB 13 8 Outdoor Unit GC 18 LT CONTENTS...
Page 87: ...APPENDIX A 15 1 SM TELECOM 1 A 0 GB APPENDIX A INSTALLATION AND OPERATION MANUAL CONTENTS...