OPTIONAL ACCESSORIES
14-4
SM TELECOM 1-A.0 GB
1
All Season Kit Installation Instruction(for ST units only)
Switch off power supply to the unit
Fig.1
Fig.2
●
Mount the Fan speed controller on the partition
of the compressor compartment in the holes pro-
vided, using four supplied screws .
Note:
●
In outdoor models OU8, the Fan Speed Control-
ler should be mounted on the partition toward the
outdoor fan motor side.
Fig.2
OU7
OU8
OU10
Fig.3
●
Unscrew the cap of the provided
service valve
D
and connect to the
T-valve
, supplied in the kit.
Use Copper sealing gasked between the
fl
are nut
and it’s connection to service valve
D
.
Note:
●
The
“T-valve”
supplied in the kit is installed be-
tween valve
D
and capillary
E
offering the possi-
bility of an additionall pressure connecting output
for service.
Fig.1
Fig.3
A
C
Additional pressure
output
E
T-valve
D
B
Service valve
cap
g
nil
a
e
s
r
e
p
o
o
C
t
e
k
s
a
g
●
Remove:
– Cover
A;
– Power panel handle
B;
–
Side cover
C
(if it exist).
CONTENTS
Summary of Contents for GC 12 LT
Page 13: ...OUTLINE DIMENSIONS 4 3 SM TELECOM 1 A 0 GB 4 5 Outdoor Unit GC 30T LT CONTENTS...
Page 28: ...CONTROL SYSTEM 11 3 SM TELECOM 1 A 0 GB 11 1 4 Main PCB Controller CONTENTS...
Page 70: ...EXPLODED VIEWS SPARE PARTS LISTS 13 6 SM TELECOM 1 A 0 GB 13 6 Outdoor Unit GC 12 LT CONTENTS...
Page 72: ...EXPLODED VIEWS SPARE PARTS LISTS 13 8 SM TELECOM 1 A 0 GB 13 8 Outdoor Unit GC 18 LT CONTENTS...
Page 87: ...APPENDIX A 15 1 SM TELECOM 1 A 0 GB APPENDIX A INSTALLATION AND OPERATION MANUAL CONTENTS...