ELECTRICAL DATA
6-1
SM TELECOM 1-A.0 GB
6. ELECTRICAL
DATA
6.1
Single Phase Units
MODEL
SX 12 TELECOM
SX 18 TELECOM
SX 30 TELECOM
Power Supply
To indoor
To Indoor
To outdoor
To Outdoor
1PH-230V-50Hz
1PH-230V-50Hz
3PH – 400V – 50 Hz
Max Current, A
7.6
12
3 x 9.2
Circuit Breaker
16
16
3 x 16
Power Supply Wiring
No. X Cross Section mm
2
3x1.5 mm
2
3x2.5 mm
2
5 X 2.5 mm
2
Interconnecting Cable RC Model
No. X Cross Section mm
2
5x1.5 mm
2
+2x0.5 mm
2
(OCT sensor)
5x2.5 mm
2
+2x0.5 mm
2
(OCT sensor)
6x1.5 mm
2
+2x0.5 mm
2
(OCT sensor)
6 X 1.5 mm
2
+ 2 X 0.5 mm
2
(OCT Sensor)
Interconnecting Cable ST Model
No. X Cross Section mm
2
4x1.5 mm
2
4x2.5 mm
5x2.5 mm
5X1.5 mm
2
+ 2X0.5 mm
2
(OCT Sensor)
CONTENTS
Summary of Contents for GC 12 LT
Page 13: ...OUTLINE DIMENSIONS 4 3 SM TELECOM 1 A 0 GB 4 5 Outdoor Unit GC 30T LT CONTENTS...
Page 28: ...CONTROL SYSTEM 11 3 SM TELECOM 1 A 0 GB 11 1 4 Main PCB Controller CONTENTS...
Page 70: ...EXPLODED VIEWS SPARE PARTS LISTS 13 6 SM TELECOM 1 A 0 GB 13 6 Outdoor Unit GC 12 LT CONTENTS...
Page 72: ...EXPLODED VIEWS SPARE PARTS LISTS 13 8 SM TELECOM 1 A 0 GB 13 8 Outdoor Unit GC 18 LT CONTENTS...
Page 87: ...APPENDIX A 15 1 SM TELECOM 1 A 0 GB APPENDIX A INSTALLATION AND OPERATION MANUAL CONTENTS...