Page 53
Technical data
English
Compressors CLS/CLC
182
202
242
302
352
Number
2
2
2
2
2
Absorbed power rating, compr. 1
kW
6
8.5
12
13.7
13.7
Absorbed power rating, compr. 2
kW
6
8.5
12
13.7
18.6
Max. absorbed power, compr. 1
kW
9
12
15
17
17
Max. absorbed power, compr. 2
kW
9
12
15
17
24
Rated current, compressor 1
A
10.1
14.4
20
24.3
24.3
Rated current, compressor 2
A
10.1
14.4
20
24.3
31.4
Max. current (FLA), compressor 1
A
15
21
24
29
29
Max. current (FLA), compressor 2
A
15
21
24
29
38.5
Max. start-up current (LRA) compr. 1
A
99
127
150
175
175
Max. start-up current (LRA) compr. 2
A
99
127
150
175
215
Oil pan resistor, compressor 1
W
70
70
65
75
75
Oil pan resistor, compressor 2
W
70
70
65
75
130
Pump (unit with 1 pump)
Supply voltage
V-ph-Hz
400 / 3 / 50
Rated power
kW
0.8
0.8
1.1
1.1
1.5
Absorbed rated current
A
1.7
1.7
3.1
3.1
3.8
Pump (unit with 2 pumps)
Supply voltage
V-ph-Hz
400 / 3 / 50
Rated power (2)
kW
0.8
0.8
1.5
1.5
1.8
Absorbed rated current (2)
A
2.1
2.1
3.8
3.8
4.9
Compressors CLS/CLC
402
502
552
602
Number
2
2
2
2
Absorbed power rating, compr. 1
kW
18.6
23
20.3
25.3
Absorbed power rating, compr. 2
kW
18.6
23
25.3
25.3
Max. absorbed power, compr. 1
kW
24
29
28
35
Max. absorbed power, compr. 2
kW
24
29
35
35
Rated current, compressor 1
A
31.4
38.5
34.3
44.2
Rated current, compressor 2
A
31.4
38.5
44.2
44.2
Max. current (FLA), compressor 1
A
38.5
47
48
59
Max. current (FLA), compressor 2
A
38.5
47
58.5
59
Max. start-up current (LRA) compr. 1
A
215
270
272
320
Max. start-up current (LRA) compr. 2
A
215
270
320
320
Oil pan resistor, compressor 1
W
130
130
150
150
Oil pan resistor, compressor 2
W
130
130
150
150
Pump (unit with 1 pump)
Supply voltage
V-ph-Hz
400 / 3 / 50
Rated power
kW
1.8
1.8
1.8
1.8
Absorbed rated current
A
4.9
4.9
4.9
4.9
Pump (unit with 2 pumps)
Supply voltage
V-ph-Hz
400 / 3 / 50
Rated power (2)
kW
1.8
1.8
1.8
1.8
Absorbed rated current (2)
A
4.9
4.9
4.9
4.9
(2) Data which refer to a single pump.