background image

5

C. 

Make the duct connections at the furnace cabinet tight. Loose connections will 

result in overheating of the component parts on the furnace and a reduction of 

the heated air flow through the duct system.

D. 

Avoid making any sharp turns in the flex duct system. Sharp turns will increase 

the static pressure in the plenum area and could cause the furnace to cycle.

E. 

Avoid  making  a  lot  of  turns  in  the  flex  duct  system.  The  straighter  the  duct 

system, the better the performance of the furnace.

F.

 

When using flex duct, insure the duct is stretched and routed straight.  Do not 

use longer length of flex duct than is needed to route directly from furnace to 

register.  Do not allow the duct to kink or accumulate.

G. 

Maintain a minimum of 1/4” clearance where ducts pass through any 

combustible construction, such as coach cabinetry. (See Figure 1.) 

NOTE

: UL 

listed duct materials can be 0” clearance.

H. 

Do not install air boosters in the duct system. Such devices will cause the 

furnace to cycle on limit and to have erratic sail switch operation.

NOTE:

 After installation of the furnace and duct system is completed, adjustments 

must be made to obtain a temperature rise within the range specified on the Rating 

Plate.

INSTALLING THERMOSTAT

The thermostat used with this unit must have NO voltage output to return leg when 

there is not a call for heat or in the “OFF” setting. 

Locate the room thermostat approximately 4-1/2 feet above the floor on an inside 

bulkhead where it is not affected by heat from any source except room air. Connect 

thermostat wiring to the blue wire and blue-white striped wire (blue-white striped 

wire is power to the thermostat) on right side of furnace. (See wiring diagram.)  If 

your furnace is equipped with a thermostat that has an adjustable anticipator, the 

anticipator should be set at .7 amps. If you desire longer heating cycles, adjust 

the anticipator to a higher setting. If you desire shorter heating cycles, adjust the 

anticipator to a lower setting. Adjustments to the anticipator setting should be made 

in .5 amp increments.

PREVENTIVE MAINTENANCE

 

WARNING

If the user of this appliance fails to maintain it 

in the condition in which it was shipped from 

the factory or if the appliance is not used solely 

for its intended purpose or if appliance is not 

maintained in accordance with the instructions 

in this manual, then the risk of a fire and/or the 

production of carbon monoxide exists which 

can cause personal injury, property damage or 

loss of life.

 

CAUTION

Label all wires prior to disconnecting for servicing and 

servicing controls. Wiring errors can cause improper and 

dangerous furnace operation.  Proper polarity MUST BE 

OBSERVED so the furnace motor will run with the proper 

direction of rotation to insure correct air delivery. (See 

wiring diagram).
Always verify proper operation of furnace after servicing.

Your furnace should be inspected by a qualified service agency yearly before turning 

the furnace on. Particular attention should be given to the following items.

1. 

Inspect furnace installation and vent termination to be sure furnace is properly 

secured in place (see Installation Instructions), that vent terminates to the 

atmosphere, and that vent tubes overlap properly (see Installing Vent Assembly.)

2. 

Inspect chamber and venting to assure that these components are physically 

sound without holes or excessive corrosion and that the installation and/

or re-installation is in accordance with Suburban’s installation instructions. 

(Reference installation manual supplied with furnace.)

 

WARNING

It is imperative that the products of combustion 

be properly vented to atmosphere and that all 

combustion air supplied to burner be drawn 

from outside atmosphere.

3. 

Check the base on which furnace is mounted. Be sure it is physically sound, 

void of any sagging, deterioration, etc.

4. 

Inspect furnace, the venting, ducting and gas piping to furnace for obvious 

signs of deterioration. Correct any defects at once.

5. 

Inspect combustion chamber for restrictions in exhaust or intake. It is imperative 

that  the  flow  of  intake  combustion  air  and  the  flow  of  exhaust  gases  being 

expelled to the outside atmosphere not be obstructed. Any soot or loose debris 

should be blown out using compressed air. (See Figure 8.)

6. 

Inspect all gaskets. If any gaskets show signs of leakage or deterioration, replace 

them. Safe operation of the furnace depends on all gaskets being tight.

7. 

Inspect return air inlet openings to the furnace. Remove any restrictions to 

assure adequate air flow.

You, as the owner/user, should inspect the furnace monthly during the 

heating season for presence of soot on vent. Operating the furnace under this 

condition could lead to serious property damage, personal injury or loss of life. 

If soot is observed on the vent, immediately shut the furnace down and contact 

a qualified service agency.

Listed below are several safety related items that you should follow during the 

heating season to assure continued safe operation of the furnace.

1. 

Inspect furnace venting. Venting must be free of obstructions, void of soot, and 

properly terminated to the atmosphere. (See Installing Vent Assembly.)

 

WARNING

Do not install screens over the vent for any 

reason. Screens will become restricted and 

cause unsafe furnace operation. Accessories 

are being marketed for RV products which we 

do not recommend. For your safety, only factory 

authorized parts are to be used on your furnace.

2. 

Periodically inspect the vent for obstructions or presence of soot. Soot is 

formed whenever combustion is incomplete. This is your visual warning that 

the furnace is operating in an unsafe manner. If soot is present, immediately 

shut furnace down and contact your dealer or a qualified service person.

3.   

Keep furnace clean. More frequent cleaning may be required due to excessive lint 

from carpeting, bedding material, etc. It is imperative that control compartments, 

burners and circulating air passageways of the appliance be kept clean.

4.   

The motor is permanently lubricated and requires no oiling.

5.   

Keep  the  furnace  area  clear  of  any  combustible  materials,  gasoline  or  other 

flammable vapor and liquids.

6.   

Before operating furnace, check the location of the furnace vent to make sure it 

will not be blocked by the opening of any door on the trailer. If it can be blocked, 

do not operate the furnace with the door open.

7. 

Do  not  restrict  the  flow  of  combustion  air  or  the  warm  air  circulation  to  the 

furnace. To do so could cause personal injury and/or death.

8. 

Never operate the furnace if you smell gas. Do not assume that the smell of 

gas is normal. Any time you detect the odor of gas, it is to be considered life 

threatening and corrected immediately. Extinguish any open flames including 

cigarettes  and  evacuate  all  persons  from  the  vehicle.  Shut  off  gas  supply  at 

Propane gas bottle. (See safety notice on front cover of this manual.)

9. 

Immediately shut furnace down and call a service agency if furnace cycles 

erratically or delays on ignition.

 

WARNING

Should overheating occur, or the gas supply 

fail to shut off, shut off the manual gas valve to 

the  appliance  before  shutting  off  the  electrical 

supply.

10.

  Never attempt to repair damaged parts. Always have them replaced by a 

qualified service agency.

11.

  Never  attempt  to  repair  the  furnace  yourself.  Seek  the  help  of  a  qualified 

service person.

12. 

Never restrict the ducting installed by your trailer manufacturer. To do so could 

cause improper furnace operation.

13. 

Do not install air boosters in the duct system. Such devices will cause the 

furnace to cycle and to have erratic sail switch operation.

14. 

Clothing  or  other  flammable  material  should  not  be  placed  on  or  near  the 

appliance.

15. 

Always follow the operating instructions. Do not deviate from the step-by-step 

procedures.

16. 

Do not use this appliance if any part has been submerged under water. 

Immediately  call  a  qualified  service  technician  to  inspect  the  appliance  and 

to replace any part of the control system and any gas control that has been 

submerged under water.

17. 

When considering add-on rooms, porch or patio, attention must be given to the 

venting of your furnace. For your safety, do not terminate furnace vent inside 

add-on rooms, screen porch or onto patios. Doing so will result in products of 

combustion being vented into the room or occupied areas.

Summary of Contents for Suburban SF Series

Page 1: ...ctric generator Contact the nearest gas supplier or qualified service technician for repairs If you cannot reach a gas supplier or qualified service technician contact the nearest fire department Do n...

Page 2: ...t be installed on vinyl siding without first consulting with the manufacturer of the siding or cutting the siding away from the area around the appliance vent In any installation in which the vent of...

Page 3: ...ied by installer Maximum wall thickness for this type installation is 2 1 Locate the furnace near lengthwise center of the coach 2 Choose a location for installation out of the way of wires pipes etc...

Page 4: ...essure equal to or less than 1 2 PSIG 1 A 3 8 male flare connection is provided for gas line hookup Some standards may require the use of a manual shut off valve in the gas line external to the furnac...

Page 5: ...f intake combustion air and the flow of exhaust gases being expelled to the outside atmosphere not be obstructed Any soot or loose debris should be blown out using compressed air See Figure 8 6 Inspec...

Page 6: ...alve at the outside Propane tank to the OFF position Do not force 3 Set thermostat above room temperature to begin blower operation A slight delay will occur before the blower comes on Allow blower to...

Page 7: ...L 2 2 3 4 DIA HOLES CL X INTAKE 1 2 MINIMUM OVERLAP EXHAUST 1 1 4 MINIMUM OVERLAP 2 3 4 DIA 2 3 4 DIA C L L C EXHAUST INTAKE 0 TO 1 1 2 520768 520968 520551 TRAILER SKIN VENT CAP MOUNTING SURFACE NEVE...

Page 8: ...IS ESSENTIAL DETAIL A VENT CAP AND EXHAUST TUBE INTAKE AIR OUTSIDE SKIN PANEL SF 20FQ SF 25FQ SF 30FQ SF 35FQ SF 42FQ STANDARD VENT INSTALLATION X INTAKE 1 2 MINIMUM OVERLAP EXHAUST 1 1 4 MINIMUM OVE...

Page 9: ...GE OF THE FRAME DOOR FRAME INTAKE TUBE 6 SCREWS SUPPLIED VENT CAP EXHAUST TUBE 4 SCREWS DOOR MOUNTING FURNACE ACCESS DOOR SECURE FRAME TO OUTER PANEL WITH SCREWS 16 PLACES GAS CONNECTION ELECTRICAL CO...

Page 10: ...ITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105 C CAUTION DO NOT HI POT DIELECTRIC HIGH VOLTAGE TEST THIS UNIT AFTER INSTALLATION TO DO SO MAY CAUSE COMPONENT DAMAGE AND VOIDS WARRANTY...

Page 11: ...11 Figure 9 INCORRECT INCORRECT CORRECT Figure 10...

Page 12: ...TIES INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY ARE HEREBY LIMITED IN DURATION TO THE PERIOD FOR WHICH EACH LIMITED WARRANTY IS GIVEN SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED W...

Page 13: ...iqu es pour la garantie de deux ann es L EXCEPTION que Suburban ne remboursera aucun frais de main d oeuvre LIMITATION DES GARANTIES LA P RIODE DE VALIDIT DES GARANTIES IMPLICITES CECI INCLUANT LES GA...

Page 14: ...alement le ventilateur et les organes de commande il ne doit rester que la chambre de combustion comme on le voit sur l illustration Injecter de l air comprim dans la chambre selon les indications des...

Page 15: ...EURS NOTE S IL EST NECESSAIRE DE REMPLACER CERTAINS CALIBRE 18 POUR TOUS LES CONDUCTEURS SAUF D AU MOINS 105 C INDICATION DIFFERENTE Figure 7 2 M A X C L 9 7 6 4 1 8 3 2 7 8 9 3 2 TUBE D ADMISSION D A...

Page 16: ...TUBE D ADMISSION D AIR BOUCHES D ADMISSION D AIR D CHARGE AVEC TUBE DE D CHARGE PANNEAU EXTERNE Figure 4 SF 20FQ SF 25FQ SF 30FQ SF 35FQ SF 42FQ INSTALLATION STANDARD DU SYST ME D ARRIV E ET DE D CHA...

Page 17: ...BOUCHE D ADMISSION D AIR D CHARGE PANNEAU EXTERNE L C Figure 2 X ARRIVE 1 2 POUNCE MINIMUM DE CHEVAUCHEMENT D CHARGE 1 1 4 POUNCES MINIMIMUM DE CHEVAUCHEMENT 2 3 4 DIA 2 3 4 DIA C L L C D CHARGE ARRIV...

Page 18: ...rrupteur d arr t est en position ON pour un fonctionnement correct 6 R gler le thermostat pour la temp rature d sir e Si cette temp rature est sup rieure celle de la pi ce le ventilateur se met en mar...

Page 19: ...ais tenter de r parer l appareil de chauffage Confier ces travaux un technicien comp tent 12 Ne jamais r duire la taille des conduits install s par le constructeur du v hicule Ceci susciterait un fonc...

Page 20: ...it traverse une paroi de mat riaux combustibles comme la paroi d un placard du v hicule maintenir un espacement d au moins 1 4 po voir Figure 3 REMARQUE L espacement peut tre nul dans le cas de condui...

Page 21: ...ouclier anti pluie fourni voir figure 1 d tail A Ne pas modifier le syst me d vacuation fourni avec cet appareil de chauffage Toute modification provoquera une d ficience de l installation pouvant sus...

Page 22: ...etc qui pourrait interf rer avec l installation Respectez les distances minimales entre l armoire et la construction combustible indiqu es dans le tableau 2 Reportez vous la figure 1 pour voir les d g...

Page 23: ...u e lors de l ouverture d une porte du v hicule Si ceci n est pas possible on doit limiter le mouvement d ouverture de la porte afin qu il y ait un espacement libre de s curit d au moins 6 po entre la...

Page 24: ...aves ou la mort Suivre les instructions et les consignes qui figurent dans la notice d utilisation qui accompagne ce g n rateur d air chaud L installation et l entretien doivent tre effectur s par un...

Reviews: