18
Connection
The module is a device which connects to the Airzone connection bus of the main board.
Control Z1-8 relay specs: Imax = 5 A at 110/250 Vac.
Note that to control elements with a greater power, it is recommended to use contactors in accordance with the power
required. Remember to connect the neutral connector directly from the circuit to the element to be controlled. Operation
It has a 5-pin terminal to connect it to the Airzone connection bus of the main board
.
Attach the wires with the terminal screws following the color code.
Power supply is connected to the module through a 3-pin terminal
. Attach the wires with the
terminal screws following the color code.
Important:
According to the current local and national regulations, it is mandatory to add a switch
(or other element to disconnect the system) to the external supply wiring so that a constant separation between poles is
guaranteed. The system will restart automatically if the supply is eventually turned off.
Configure the AZRA6CM1VALC module according to your installation. To do this you must leave the LED that corresponds to
your installation on:
1.
Press the operation relays configuration button for 2 s.
2.
Switch between the different configurations by pressing the same button.
3.
Save the configuration by another 2 s pressing in the same button.
Configuration /
Relay output
Configuration 1
Configuration 2
Configuration 3
R1
On/Off
Pump
*
On/Off
Pump
*
Cooling Mode: On
Heating Mode: Off
Stop Mode: Off
R2
Cooling Mode: On
Heating Mode: Off
Stop Mode: On/Off**
Cooling Mode: Off
Heating Mode: On
Stop Mode: On/Off**
Cooling Mode: Off
Heating Mode:
On
Stop Mode: Off
* The relay R1 is activated when demand is generated in the system with a 3-minute delay.
** The relay R2 maintains the last requested mode, prior to the Stop mode.
LEDs configuration selected