28
Important:
In order to optimize the production temperature of the aerothermal units, the following combinations will not
generate air demand in the production control board:
-
Communication gateway (AZX6QADAPTxxx / AZX6QADAPT3xxx) in Flexa 3.0, Innobus Pro6, Acuazone and Innobus
Pro32 main control boards.
-
Controller 3.0 gateway (AZX6GTCxxx) in Flexa 3.0, Innobus Pro6, Acuazone and Innobus Pro32 main control boards.
-
Communication gateway for electromechanical units (AZX6ELECTROMEC) in Flexa 3.0, Innobus Pro6, Acuazone and
Innobus Pro32 main control boards.
-
Infrared gateway module (AZDI6MCIFR [C/R]) in Acuazone e Innobus Pro32 systems (when configured as a zoning
system or mixed system).
-
Gateway module (AZDI6MCIFR [C/R]) in Acuazone e Innobus Pro32 systems (when configured as a zoning system or
mixed system).
Important:
To guarantee the optimization of the production temperature of the aerothermal units, these device combinations
do not generate radiant demand to the production control board:
-
Zoning module for Electrical Heating Element (AZDI6MZSRE [C/R]) in Acuazone and Innobus Pro32 systems regardless
of the Main Control Board configuration.
SW2
To force the production control board to search for the connected systems and save the configuration of the
installation, press SW2.
Configuration
It is required to configure the relays control logic for the production control board, as well as the other
parameters of the cloud production control board. The cloud production control board settings are only available in the master
Blueface thermostat of the system nº1
(see section Production Parameters).
AIRZONE PRODUCTION CONTROL BOARD (AZX6CCP)
Assembly
The production control board is supplied in a patter that is screwed to Wall for a better fixing.
It is should be placed and mounted in accordance with the current electronic regulations. For
the mounting of the main control board, follow the following steps:
•
Locate the control board close to the unit to be controlled.
•
Unscrew the cover securing the back part to the wall.
•
Make all the connections and screw the cover again.