Error C-09: Aerothermal Gateway-Production Control Board Communication Error
The system loses communication with the Gateway and, therefore, with the aerothermal system. The control of the system will
be disabled, enabling the system to work from the manufacturer’s thermostat. To solve this incident check:
1.
Verify that the Gateway is properly connected to the unit port of the Production Control Board.
2.
Check the status of the LEDs of the gateway. To do this check the self-diagnose section or the technical sheet of the
gateway.
Error C-11: Aerothermal Gateway- Aerothermal indoor unit Communication Error
The system loses communication with the aerothermal system. The control of the system will be disabled, enabling the system
to work from the manufacturer’s thermostat. To solve this incident verify that the Gateway is properly connected to the
Domotic Bus of the Cloud Production Control Board AZX6CCPWSCC and the connection between the Gateway and the
Aerothermal indoor unit.