19
AIRZONE WIRED THERMOSTATIC VALVE ACTUATOR 110/230V VALC FOR RADIANT ELEMENTS
(AZX6AC1VALC)
Assembly
Airzone wired thermostatic valve actuators are mounted on each of the valves of a manifold / heater. Check that the
thermostatic valve actuator is compatible with the valve body that you are going to equip (M30 x 1.5).
Connection
Airzone wired thermostatic valve actuators are connected to the Z1-8 ports of the AZRA6CM1VALC module.
Connect throught 2 wires without polarity.
Important:
Use a suitable screwdriver to press in the locking tabs.
Maximum number of valves permitted: 2 for each output (20 valves in total).
AIRZONE WIRED THERMOSTATS (AZRA6BLUEFACEC / AZRA6THINKC / AZRA6LITEC)
Assembly
Wired thermostats are mounted on the wall through a support. It is recommended not to locate it more than 40 meters away
from the main control board. To fix it to the wall, follow these steps:
•
Separate the back part of the thermostat from the wall support and make all the
connections.
•
Fix the back part of the thermostat to the wall.
•
Place the display on the support once it is fixed.
•
Place the anti-theft rods for additional support (optional).
Summary of Contents for 8435418928905