35
ASSEMBLY AND CONNECTION EVALUATION
Check the following aspects:
-
The state of the LEDs of the main control board and the rest of control elements. Check the self-diagnose section of
the data sheet of the elements.
-
If all the thermostats are powered.
INITIAL CONFIGURATION
AIRZONE BLUEFACE AND THINK THERMOSTATS
Important:
Once you start the process, it cannot be interrupted. You will be able to modify the desired parameters later.
Language/Country
Select your language and country. These are the available languages: Spanish, English, French, Italian, Portuguese and German.
To associate a wireless Think thermostat, start the radio channel search:
Setting wireless device
-
Open the radio channel. To do that, press on SW1. The LED D11 will remain solid red. Once open,
you have 15 minutes to make the association. If that period of time expires, start the process
over again. Remember not to open more than one module at the same time, it may alter the
process. You can also open the channel association radio through the Blueface and Think (see
section
IMPORTANT:
not to open more than one radio channel at the same time, it may alter the
process.
-
Start the radio channel search, to do so, press Airzone to start the search.
-
The controller will display the different wireless zone modules found, with the signal level of each one of them. Select
the wanted module and press “Check”, the selected module will begin to “beep” to be identified. Verify the range is
correct (30% minimum) and confirm.
Zone address
Select the zone associated to the thermostat. Each zone corresponds to a radiant element relay output (AZRA6CM1VALC).
Associated outputs
If necessary, the system allows you to associate more than one control output to a zone. It is possible to control multiple outputs
from the same thermostat.
Thermostat configuration
Select the operation of the thermostat:
-
Master: Controls all the parameters of the installation.
-
Zone: Controls all the parameters of the zone.
Control stages
Enables/Disables the radiant stage with cooling and heating modes and select your type of installation*.
* In case of selecting Electric in the type of installation, no radiant demand is generated in the CCP and the zone always works in
heating mode, regardless of the operating mode of the system.
Other settings
Access the advanced settings (system address, temperature range, etc.) to change other settings or activate the basic function
if you want to (see
Summary of Contents for 8435418928905
Page 1: ...r e b m u N e g a P d r a o b p il C Installation Manual RADIANT365 AZRA6RADIANT AZRA6CM1VALC...
Page 2: ...1 8 ZONES AZRA6RADIANT AZRA6CM1VALC...
Page 35: ...36 Blueface Think Important Use to confirm and to return...