SYSTEM PARAMETERS
•
System address.
Use this parameter to define the system number in your installation using this parameter. The
Supermaster
option
(available in installations with Airzone production control board, AZX6CCP / AZX6CCPWSCC)
allows
you to impose the operation mode of the system to the rest of the systems connected to the CCP in a semi-forced way:
•
Temperature range.
Use this parameter to select the highest temperature in heating mode (19-30 ºC, by default 30ºC)
and the lowest temperature in cooling mode (18-26 ºC, by default 18ºC). It is also possible to disable some of the
modes.
•
Hysteresis Configuration.
Defines the temperature differential between the room temperature and the set-point
temperature required to start applying the Algorithm RadianT.
This algorithm prevents overheating in underfloor air
conditioning installations. If your installation has radiators, set this value to 0ºC. (By default 2ºC)
•
Radio channel.
It activates/deactivates the wireless association module of the system.
•
Condensation
protection
(only available for thermostat Blueface on installations with cooling radiant control)
. Enables
to select the protection level against condensation: Very high, high, medium (by default), low and very low. If
necessary, it can be activated for 1h.
*Note
: In Very Low configuration, the humidifier will be automatically activated if the relative humidity level is higher
than 55% in any active zone.
•
Reset system
(only available for master thermostat Blueface)
.
Resets the system and returns to factory settings. To
reconfigure the thermostats, please check
•
Information
(only for Think thermostats)
.
It provides information about the zone, the system, the devices and the
Webserver.
ZONE PARAMETERS
•
Associated outputs.
It displays and allows you to select the control outputs associated with the thermostat.
•
Thermostat settings.
Use this parameter to define the thermostat as Master or Zone.
*Note:
It cannot be configured as Master if there is already another Master thermostat.
•
Use mode.
The thermostats can be set in Basic or Advanced mode. They are set in Advanced mode by default. These
are the parameters you can control in basic mode: On/off and set-point temperature.
If you need to reset the thermostat to Advanced mode, access the advanced configuration menu and then activate
the advanced use mode.
•
Control stages.
This parameter is used to configure both cooling and heating stages in a single zone or in all the zones
and your type of installation*.
* In case of selecting Electric in the type of installation, no radiant demand is generated in the CCP and the zone always works
in heating mode,
regardless of the operating mode of the system
.
•
Offset.
Correction factor for the room temperature of the zones (range: from -2.5ºC to 2.5 ºC in steps of 0.5 ºC). It is in
0ºC by default.
•
Reset thermostat.
It resets the thermostat and returns it to factory values.
Operation mode:
System 1
Available operation modes:
Rest of the systems
Summary of Contents for 8435418928905
Page 1: ...r e b m u N e g a P d r a o b p il C Installation Manual RADIANT365 AZRA6RADIANT AZRA6CM1VALC...
Page 2: ...1 8 ZONES AZRA6RADIANT AZRA6CM1VALC...
Page 35: ...36 Blueface Think Important Use to confirm and to return...
Page 49: ...50 NAVIGATION TREES NAVIGATION TREE BLUEFACE THERMOSTAT...