PRODUCCTION PARAMETERS
The configuration parameters of the Production control board (AZX6CCPWSCC) settings are only available in the master
Blueface thermostat of the system nº1.
•
Operation logic.
It
allows to configure the operation logic for the control relays of the production control board:
-
Aerothermal unit (Default preset)
-
2 pipes
-
4 pipes
-
RadianT
(Recommended for RadianT365 systems)
•
Activation delay.
It allows to set a delay time in the power on of the production unit, configurable in minutes, from 0
to 7. (Default preset to 3 minuts).
•
LWT temperatures.
(Only available in installations with AZX6GAW XXX control gateways)
It allows to set the LWT
temperaturas for the heatting and cooling modes of the aerothermal unit. Selectable values depends on each
particular aerothermal unit. Default presets are:
-
Air in cooling mode: 10 ˚C
-
Radiant in cooling mode: 18 ˚C
-
Air in heating mode: 50 ˚C
-
Radiant in heating mode: 35 ˚C
•
DHW function.
(Only available in installations with AZX6GAW XXX gateways)
It allows to turn on/off the Domestic Heat
Water (DHW) function in the systems connected to the CCP. Activated by default.
•
Cooling mixing valve
(only available in installations with AZX6GAW XXX gateways)
.
Select "Auto" if you have mixing
valves for cooling in your installation. It is set to Manual by default.
SELF-DIAGNOSE
AIRZONE BLUEFACE AND THINK THERMOSTATS (AZRA6BLUEFACEC / AZRA6THINK [C/R])
Blueface and Think Thermostats Warnings
Thermostat displays all the system warnings on the screensaver. If there is any error, it will be displayed on the screensaver, on
the main screen and on “About errors”, in user settings.
•
Anti-freezing
:
It will be only displayed when it is activated. (See
Zone settings – Blueface thermostats
).
•
Active dew protection
. It indicates there is a risk of condensation in the radiant stage and the air stage has been
activated to avoid its creation.
•
Dew
. This alert warns of a risk of water condensation and the zone has been shut off, turning on the dehumidifier if it
has been installed. Only available in systems with radiant stages in cooling mode.
•
Lite dew protection
.
(only Blueface)
It indicates there is a risk of condensation in the radiant stage and the air stage
has been activated to avoid its creation in the Lite zone.
•
Dew Lite.
(only Blueface)
It indicates there is a risk of condensation and the zone where the Lite thermostat is located
has been turned off. Press the icon to know which zone is affected.
•
Battery Lite
(only Blueface)
.
Low battery warning. Informs about the involved zone when the icon is pressed.
•
Battery
(only Think wireless).
Low battery warning.