22
ES
EN
FR
IT
PT
DE
THERMOSTAT
Warning
•
Anti-freezing.
It will be only displayed when it is activated. (See User manual for more information).
•
Active window.
It indicates the air conditioning of the zone has been deactivated due to open window. Only available
if the window contact of the system is activated.
•
Active presence.
It indicates no occupancy has been detected in the zone for the last 5 minutes. Therefore, the Sleep
mode is activated (the zone will switch off after 90 minutes). Only available for systems with occupancy control.
•
Low Battery.
Low battery warning. It has 2 weeks of life left in normal conditions.
Errors
Error 1: Wired thermostat-Main control board communication error
This incident blocks the control of the zone. To solve this incident check:
1.
Main control board status: Correctly powered.
2.
Main control board status: Thermostat connection bus LEDs are operating properly.
3.
Connection: Verify the polarity of the main control board and thermostat connectors.
4.
Wiring: Check that the voltage between the poles (A/-) and (B/-) is about 0.65 Vdc.
5.
Restart the zone and re-associate it with the system:
-
Blueface thermostats: Press on Reset to restart the device. If the error persists, press and hold on
and reset the
thermostat. Configure the system.
-
Think thermostats: To do this, press and hold on
and restart the start-up configuration process.
Note:
If the system is restarted, this error may be displayed in the thermostats at the beginning of the process. This message
should disappear after around 30 seconds.
Error 1: Wireless Thermostat-Main control board communication error
This incident blocks the control of the zone. To solve this incident check:
1.
Thermostat status: Check the signal range of the thermostat with the main control board through the Information
parameter (
See user manual)
or move the thermostat closer to the main control board. If that way the communications
are reestablished, it means it is necessary to relocate it permanently as it was out of range.
2.
Main control board status: Correctly powered.
3.
Main control board status: Proper operation of the LED of wireless communication.
4.
Restart the zone and re-associate it with the system. To do this, press and hold on
and restart the start-
up configuration process. Note that, if you need to associate wireless devices, the wireless association module must
be previously open from main control board.
Note:
If the system is restarted, this error may be displayed in the thermostats at the beginning of the process. This message
should disappear after around 30 seconds.
Error 5: Temperature probe - Open circuit
The zone ceases to measure the room temperature; therefore, the zone cannot generate demand. Proceed to replace it of the
device or sent it for repair.