The default setting is Automatic mode, imposing airflow based on the number of zones on
demand. Depending on the type of installation, it will be possible to select the speed manually
from the master thermostat.
Fan speed
High speed
Low speed
Medium speed
Automatic speed
On/Off.
Pressing the icon turns the zone in which the thermostat is located on or off.
Cooling.
In this operation mode, the system only operates with the AC unit in cooling mode
when any of the zones associated to the system is generating demand (set-point temp. < room
temp.).
Heating.
In this operation mode, the system only operates with the AC unit in heating mode
when any of the zones associated to the system is generating demand (set-point temp. > room
temp.).
Ventilation.
In this operation mode, the system only operates with the AC unit in ventilation
mode when any of the zones associated to the system is generating demand (set-point temp. <
room temp.).
This is managed from the master thermostat, press to access the selection menu. The available
modes are as follows:
HVAC control
Operation mode
23.5°
Set-point temperature.
Using the - and + signs that appear when you press on the
temperature, you can select the desired set-point temperature, in steps of 0.5°C.
The temperature range permitted in heating mode is: 15-30°C. In cooling mode: 18-30°C. These
vary depending on the level of efficiency (Eco-Adapt) that has been selected on the master
interface.
Zone settings
Press on the icons to access the parameters:
Anti-freezing.
Prevents the room temperature in the zone from dropping below 12°C, even
if the zone is off. (In Stop mode it will not be activated).