34
EN
System Installation
EASYZONE PLENUM ASSEMBLY
Use threaded rods to fix the Easyzone to
the ceiling through the tabs found at each
end.
It is recommended to insulate all metal parts of the Easyzone that remain in contact with the
outside to prevent condensation.
Locate the drilling holes; if they are
covered, use a screwdriver to uncover them
to fix the Easyzone to the unit.
Important: If your unit has a front with
circular adapters, remove this and mount
the supplied adapter.
Place the Easyzone over the unit's supply
vent and fix it using the screws.
Be sure to insulate the connection neck.
Use strips of 25 mm thick insulation
material (glass wool or polyethylene
foam). The width of these insulation strips
is 97 mm for the Standard and Medium
motorized plenum and 37 mm for the Slim
motorized plenum.
Assembly in the indoor unit