Error 1: Thermostat (wired) - Main control board
This issue does not allow the zone to be controlled. Check whether the error appears on all
thermostats; if it does, check that the main control board is operating properly. To resolve this
issue, make the following checks:
1.
Status of the main control board: Check that the power supply is correct.
2.
Status of the main control board: Correct operation of the Airzone connection bus LEDs.
3.
Connections: Check that the polarity of the connections to the main control board and the
thermostat is correct.
4.
Wired: Check that the voltage between poles (A /-) and (B/-) is 1.8 VDC.
5.
Restart the zone and reassociate it to the system:
•
Blueface thermostats: Press on the word Reset to restart the device. If the error persists,
press and hold the icon and reset the thermostat. Carry out the initial configuration of the
system.
•
Think thermostats: Press and hold on
and perform the initial system
configuration process.
6.
Restart the system: If you restart the system, this error may appear on the thermostats due
to the restart. This message should disappear in approximately 30 seconds once the restart
has been completed.
Blinking
1.8Vdc
ERROR 1