Error 10: BACnet gateway - Main control board
Error 11: Gateway - Indoor unit
The system loses communication with the gateway. Check that the gateway is properly
connected to the main control board's DM1 port.
D34 D35
D3
D11
D9
D8
The gateway loses communication with the AC unit. The system will open all its zones and
disable control from the system's thermostats, thus allowing the AC unit to operate from the
manufacturer's thermostat. To resolve this issue, make the following checks:
1.
Check that the AC unit is powered. To do this, check that the AC unit's thermostat is
switched on.
2.
Check whether the AC unit operates properly independently of the system. To do so,
disconnect the AC unit from the Airzone system and activate the unit from the AC unit's
thermostat.
3.
Connections: Check that the polarity of the connections to the gateway and indoor unit is
correct. Consult your gateway's technical fact sheet.
4.
Wired: In DIN rail gateways, check that the voltage between poles (A /-) and (B/-) is 1.8 VDC.
5.
Check that the status of the connected gateway's LEDs is correct. To do so, make use of the
troubleshooting section or your gateway's technical fact sheet.
1.8Vdc
Gateway in
DIN format