58
EN
Error 15: Consumption meter - Main control board
Error 16: Measuring error in consumption meter
This incident doesn't allow you to measure the AC unit’s
consumption. To resolve this issue, make the following checks:
1.
Signal range of the device: Check the signal range of the meter
with the main control board; to do so, check the LED
on
the meter. If it is not in signal range (red LED), bring the meter
closer to the main control board. If it recovers communications,
it will be necessary to relocate it because it was out of range.
2.
Status of the consumption meter: Check that the power supply
is correct.
This incident doesn't allow you to measure the AC unit’s consumption. To resolve this issue,
make the following checks:
Check that the ammeter clamp is properly connected to the AC unit wiring.
Error 17: Lutron gateway - Airzone system
The system loses communication with the gateway. Check that the gateway is properly
connected to the main control board's DM1 port.