Error IAQ3: Zone module with ionizer not connected
Error IAQ4: Actuator connected directly without ionizer
This warning indicates that an ionizer has not been detected in a zone and is generated when
ionization is started in a zone. To resolve this issue:
1.
Check that the polarity of the connections between the IOx port and the Ionizer is correct.
2.
Check the ionization status LEDs on the main control board.
Purification
This error occurs when an actuator is directly connected to the outputs intended for the
ionization boards on the main control board. It can cause the actuators to stop running.
If you reset the system, the error will become IAQ3 and will allow ionization in all zones except
this one.
You can resolve this issue by following the steps below:
1.
Check that you have not connected an actuator directly to the main control board.
2.
Check the connections between the actuator and the ionizer, as well as between the ionizer
and the main control board.