Unoccupied.
This mode aims to short periods of absence. Avoids the temperature to surpass the established limit
temperature for cooling and heating mode, generating demand with a set-point temperature previously
established by the installer (27˚ C / 81˚ F in cooling mode and 17.5˚ C / 63˚ F in heating mode by default) for
returning to the allowed values, as long as the zone is on.
When interacting with the zone while this mode is selected, the controller displays the unoccupied override
warning. If the set-point temperature is changed, it is maintained for the pre-established period of time (60 minutes
by default) and returns to the set-point temperature of the unoccupied mode.
Vacation.
This mode aims to long periods of absence. It turns off all the zones to save energy and turns them on
avoiding the temperature to surpass the established limit temperature (35˚ C / 95˚ F in cooling mode and 10˚ C /
50˚ F in heating mode), generating demand with the previous set-point temperature before activating the vacation
mode.
When interacting with the zone while this mode is selected, the controller displays the vacation override warning.
If the set-point temperature is changed, it is maintained for the pre-established period of time (60 minutes by
default) and turns off the zones again.
Stop.
The air-conditioning system will remain switched off regardless of the demand status of any zone, all the
motorized dampers will remain opened.
Airflow control.
This parameter is only available when the controller is configured as main of a zoned system, selects the
control algorithm that best fits the installation. The available options are:
Silence.
The fan speed is lower than in standard mode to reduce the noise.
Standard.
Set by default. The system automatically regulates the fan speed based on the number of zones calling
for cooling or heating.
Power.
The fan speed is higher than in standard mode to increase the flow.
Fan Speed.
This parameter is only available when the controller is configured as main in Fancoil installations or in zones with
individual units. It is used to set the fan speed of the AC unit fan. The airflow control is set in automatic speed by default.
High speed.
Medium speed.
Low speed.
Automatic speed.
Depending on the unit, enables to directly select the speed of the unit, setting the value 1 as the lowest speed. The speed
is set as auto by default.
Note:
For security reasons, the zone will turn off after changing any setting.
Local Ventilation.
This option enables the activation
or deactivation
of the ventilation in the selected zone when the
system is not actively cooling or heating any of the zones.
Timer.
It is an auto power-off timer of the zone:
Off.
Timer is not activated.
30.
It activates the timing and switches off the zone after 30 minutes.
60.
It activates the timing and switches off the zone after 60 minutes.
90.
It activates the timing and switches off the zone after 90 minutes.
Information.
This parameter provides information about:
•
Zone: firmware, zone, association, actuator or communication status.
•
System: firmware, settings and information about the system controllers.
•
Devices: displays the elements connected to the system.
•
Webserver (Only for system 1 Main controller): firmware, IP address, gateway, MAC and PIN.
Main zone.
This parameter is only available when the Main controller of the group is lost. Enables to access and to modify the
operation mode of the group.