17
EN
EN
FR
IT
PT
DE
WARNINGS AND ERRORS
Controller displays all the system warnings on the screensaver.
Warnings
Unoccupied Override.
A zone has been activated while the user mode is set on
Unoccupied. If the set-point temperature is changed, it is maintained for the pre-
established period of time (60 minutes by default) and returns to the set-point
temperature of the unoccupied mode.
Vacation Override.
A zone has been activated while the user mode is set on
Vacation. If the set-point temperature is changed, it is maintained for the pre-
established period of time (60 minutes by default) and turns off the zones again.
Window.
The air conditioning of the zone has been suspended due to open
window. Only available if the window contact of the system is activated.
Occupancy.
No occupancy has been detected in the zone for the last 5 minutes.
Therefore, the timer is activated (the zone will switch off after 90 minutes). Only
available if the presence contact is activated.
Low Battery.
Displayed when the interface has low battery. It has 2 weeks of life
left in normal conditions.
Heat supply activated.
The Heat supply of the cool mode is activated.
Errors
If any of these errors occurs, please contact with your installer.
Error 1.
Communication error with the control module.
Error 2.
Communication error with the main control board.
Error 3.
Motorized element not connected to the actuator output.
Error 4.
Unusual behavior of the motorized element.
Error 5.
Temperature sensor is opened.
Error 6.
Temperature sensor is short circuited.
Error 9.
Communication error between the communications gateway and the system.
Error 10.
Communication error between the BACnet interface and the main control board.
Error 11.
Communication error between the communications gateway and the indoor unit.
Error 12.
Communication error between the webserver and the main control board.
Error 13.
Communication error between the main control board and the control module of radiant elements.
Error 17.
Communication error between the Lutron interface and the main control board.
Summary of Contents for AZPRBLUECOSG