Operation Mode
This parameter is only available when the controller is configured as main. To change the Operation Mode from the Home
Screen, press the Operation Mode icon and swipe left or right to select the desired operation mode:
Cool.
In this mode, the conditioning unit will start a cooling cycle any time that any zone is in cool demand (T
Set-Point
< T
room
).
It enables to activate the heat supply function.
Note:
The heat supply function is only available for individual zone modules.
Heat.
Enables the heating cycle whenever a zone is in heating demand (T
Set-Point
> T
room
).
Auto.
The Auto mode allows automatic switching between cool and heat, depending on the global demand.
Dry.
Only available in direct expansion systems. The system works in dry mode, refreshing the zone (reducing the humidity)
when any of the zones is generating demand (T
Set-Point
< T
room
).
Note
: Dry mode decreases humidity in the room by entering the dehumidification cooling cycle.
Emergency Heat.
This mode activates the Auxiliary Heat to provide heated air in case of a mechanical failure in the system.
Note:
This mode is only visible when the installation includes an auxiliary heating device.
User Mode
This parameter is only available when the controller is configured as main. To change the User Mode from the Home Screen,
press the User Mode icon and select the desired mode:
Comfort.
Default and standard user mode. The desired set point temperature can be selected using the predefined
temperature ranges.
Eco.
The range of available set point temperatures adapts for getting a more efficient operation.
Night time.
The system automatically changes the set point temperature 0.5˚ C/1˚ F every 30 minutes in up to 4 increments
of 2˚ C/4˚ F in 2 hours. When cooling, the system increases the set point temperature; when heating, the system decreases
the set point temperature.
Unoccupied.
This mode aims to short periods of absence. Avoids the temperature to surpass the established limit
temperature for cooling and heating mode, generating demand with a set-point temperature previously established by the
installer (27˚ C / 81˚ F in cooling mode and 17.5˚ C / 63˚ F in heating mode by default) for returning to the allowed values, as
long as the zone is on.
When interacting with the zone while this mode is selected, the controller displays the unoccupied override warning. If the
set-point temperature is changed, it is maintained for the pre-established period of time (60 minutes by default) and returns
to the set-point temperature of the unoccupied mode.
Vacation.
This mode aims to long periods of absence. It turns off all the zones to save energy and turns them on avoiding
the temperature to surpass the established limit temperature (35˚ C / 95˚ F in cooling mode and 10˚ C / 50˚ F in heating
mode), generating demand with the previous set-point temperature before activating the vacation mode.
When interacting with the zone while this mode is selected, the controller displays the vacation override warning. If the set-
point temperature is changed, it is maintained for the pre-established period of time (60 minutes by default) and turns off
the zones again.
Stop.
The air-conditioning system will remain switched off regardless of the demand status of any zone, all the motorized
dampers will remain opened.
Airflow
This parameter is only available when the controller is configured as main. Select the control algorithm that best fits the
installation. The available options are:
Silence.
The fan speed is lower than in standard mode to reduce the noise.