Error 8: Wired Lite thermostat not found
The zone ceases to measure the room temperature of an associated wired Lite thermostat; therefore, the zone cannot generate
demand. Check which Lite thermostat is not working properly. To solve this incident check:
1.
Connection: Check the polarity of the main control board and thermostat connectors.
2.
Wiring: Disconnect the terminal from the Airzone connection bus and check that the voltage between the poles (A/-)
and (B/-) is about 0.65 Vdc.
3.
Verify the thermostat microswitch corresponds with the zone associated. If not, activate it using the tab with the value
needed.
Remember:
If you need to change the zone number, reset the thermostat and start association process.
Error 8: Wireless thermostat Lite not found
The zone ceases to measure the room temperature of an associated wireless Lite thermostat; therefore, the zone cannot
generate demand. Check which Lite thermostat is not working properly. To solve this incident check:
1.
Power supply: Check the battery and replace it if necessary.
2.
Verify the thermostat microswitch corresponds with the zone associated. If not, activate it using the tab with the value
needed. Note that, if you need to associate wireless devices, the wireless association module must be previously open
(from SW1 button or from any thermostat, pressing
Wireless module
inside
Advanced settings, zone parameters).
Remember:
If you need to change the zone number, reset the thermostat and start association process.