Error 12: Main Board-Webserver communication error
The system loses the communication with the webserver. Check the connection of the webserver to the Main board domotic
bus.
Error V01: Main Board and AZX6CM1VALR module communication error
This incident blocks the control of the zone. To solve this incident check:
1.
Status of the control module of the radiant elements: Correctly powered. Check the polarity of the connectors of the
main control board and the module.
2.
Status of the control module of the radiant elements and the main control board: Airzone connection bus LEDs are
operating properly.
3.
Wiring: Disconnect the terminal from the Airzone connection bus and check that the voltage between the poles (A/-)
and (B/-) is about 1 Vdc.