31
Error V02: Communications error between AZX6CM1VALR module and AZX6AC1VALR head
This issue does not allow the system to control the device. To resolve this issue, check:
1.
Communication between AZX6CM1VALR module and AZX6AC1VALR head.
2.
Appropriate distance to ensure signal range between head and module.
3.
Maximum distance in open space: 40 m.
Error C-02: Main Control Board – Production Control Board communication error
This incident blocks the control of the zone. To solve this incident check:
1.
Status of the control module of the radiant elements: Correctly powered.
2.
Status of the Main Control Board: Airzone connection bus LEDs are operating properly.
3.
Connection: Check the polarity of the connectors of the CCP and the Main Control Board of the system.
Error C-09: Aerothermal Gateway-Production Control Board Communication Error
The system loses communication with the Gateway and, therefore, with the aerothermal system. The control of the system will
be disabled, enabling the system to work from the manufacturer’s thermostat. To solve this incident check:
1.
Verify that the Gateway is properly connected to the unit port of the Production Control Board.
2.
Check the status of the LEDs of the gateway. To do this check the self-diagnose section or the technical sheet of the
gateway.