26
•
Information
(only for Think thermostats)
.
It provides information about the zone, the system, the devices and the
Webserver.
ZONE PARAMETERS
•
Thermostat settings.
Use this parameter to define the thermostat as Master or Zone (only available in Blueface).
*Note:
It cannot be configured as Master if there is already another Master thermostat.
•
Use mode.
The thermostats can be set in Basic or Advanced mode. They are set in Advanced mode by default. These
are the parameters you can control in basic mode: On/off and set-point temperature.
If you need to reset the thermostat to Advanced mode, access the advanced configuration menu and then activate
the advanced use mode.
•
Offset.
Correction factor for the room temperature of the zones, range from:
o
Zones with Thermostat:
-2.5ºC to 2.5 ºC in steps of 0.5 ºC.
o
Zones without Thermostat:
-5ºC to 5 ºC in steps of 1 ºC.
•
Reset thermostat.
It resets the thermostat and returns it to factory values.
PRODUCTION PARAMETERS
•
Operation logic.
It
allows to configure the operation logic for the control relays of the
AZX6CCPWSCC
:
•
Aerothermal unit (Default preset)
•
2 pipes
•
4 pipes
•
RadianT
(Recommended for RadianT365 systems)
•
Activation delay.
It allows to set a delay time in the power on of the production unit, configurable in minutes, from 0
to 7. (Default preset to 3 minuts).
•
LWT temperatures.
(Only available in installations with AZX6GAW XXX gateways)
It allows to set the LWT temperaturas
for the heatting and cooling modes of the aerothermal unit. Selectable values depends on each particular aerothermal
unit. Default presets are:
•
Air in cooling mode: 10 ˚C
•
Radiant in cooling mode: 18 ˚C
•
Air/Radiator in heating mode: 50 ˚C
•
Radiant in heating mode: 35 ˚C
•
DHW function.
It allows to turn on/off the Domestic Heat Water (DHW) function. Activated by default.
•
Cooling mixing valve.
(Only available in installations with AZX6GAW XXX gateways)
Select "Auto" if you have mixing
valves for cooling in your installation. It is set to Manual by default.