Error C-11: Aerothermal Gateway- Aerothermal indoor unit Communication Error
The system loses communication with the aerothermal system. The control of the system will be disabled, enabling the system
to work from the manufacturer’s thermostat. To solve this incident verify that the Gateway is properly connected to the
Domotic Bus of the Cloud Production Control Board AZX6CCPWSCC and the connection between the Gateway and the
Aerothermal indoor unit.
AIRZONE LITE THERMOSTAT (AZRA6LITE [C/R])
Lite thermostats incorporate LEDs that detect malfunctioning.
Status LED
blinking red quickly: Wired Lite Thermostat-Main control board communication error
This incident blocks the control of the zone. Check that "Error 1" not appear in all thermostats. If so, verify the proper operation
of the main board. To solve this incident check:
1.
Main control board status: Correctly powered.
2.
Main control board status: Airzone connection bus LEDs are operating properly.
3.
Connection: Verify the polarity of the main control board and thermostat connectors.
4.
Wiring: Disconnect the terminal from the Airzone connection bus and check that the voltage between the poles (A/-)
and (B/-) is about 0.65 Vdc.
5.
Restart the zone and re-associate it with the system. To do this, pull down all the microswitchs, reinsert the thermostat
in its base and press on the thermostat. The LED
will flash green twice when the reset process is completed.
6.
Restart system: If the system is restarted, this error may be displayed in the thermostats at the beginning of the process.
This message should disappear after around 30 seconds.