Z. 13

 

Z. 14

 

Object number 

27 

43 

59 

75 

91 

107 

123 

139 

155 

171 

187 

203 

219 

235 

Name 

Zone X - Set-point temperature 

Function 

Temperature 

Description 

It is used to define the set-point temperature value. It is possible to select any available zone.  

Values  

Celsius degrees format: 0ºC…99ºC, in steps of 0,5ºC 

Type of bus access 

Writing 

Data point identification 

9,001 

 

 

Z. 1

 

Z. 2

 

Z. 3

 

Z. 4

 

Z. 5

 

Z. 6

 

Z. 7

 

Z. 8

 

Z. 9

 

Z. 10

 

Z. 11

 

Z. 12

 

Z. 13

 

Z. 14

 

Object number 

28 

44 

60 

76 

92 

108 

124 

140 

156 

172 

188 

204 

220 

236 

Name 

Zone x – Relative humidity 

Function 

Humidity 

Description 

It is used to read the relative humidity value.  

Values  

0=0% ... 100=100% 

Type of bus access 

Reading 

Data point identification 

9,007 

 

 

Z. 1

 

Z. 2

 

Z. 3

 

Z. 4

 

Z. 5

 

Z. 6

 

Z. 7

 

Z. 8

 

Z. 9

 

Z. 10

 

Z. 11

 

Z. 12

 

Z. 13

 

Z. 14

 

Object number 

29 

45 

61 

77 

93 

109 

125 

141 

157 

173 

189 

205 

221 

237 

Name 

Zone X - Local temperature 

Function 

Temperature 

Description 

It is used to define the local temperature value. In order to make zones without Airzone 
elements work, it is required to write the room temperature from this object. 

Values  

0ºC…99,9ºC, in steps of 0,1ºC 

Type of bus access 

Reading 

Data point identification 

9,001 

 

 

Z. 1

 

Z. 2

 

Z. 3

 

Z. 4

 

Z. 5

 

Z. 6

 

Z. 7

 

Z. 8

 

Z. 9

 

Z. 10

 

Z. 11

 

Z. 12

 

Z. 13

 

Z. 14

 

Object number 

30 

46 

62 

78 

94 

110 

126 

142 

158 

174 

190 

206 

222 

238 

Name 

Zone X - Local temperature 

Function 

Temperature 

Description 

It is used to define the local temperature value. In order to make zones without Airzone 
elements work, it is required to write the room temperature from this object. 

Values  

0ºC…99,9ºC, in steps of 0,1ºC 

Type of bus access 

Writing 

Data point identification 

9,001 

 

 

 

Summary of Contents for AZX6KNXGTWAY

Page 1: ...r e b m u N e g a P d r a o b p il C Installation Manual...

Page 2: ...3 Precautions 3 Environmental policy 3 General requirements 3 Introduction 4 Assembly 4 Connection 4 Configuration 5 General recommendations 6 Configuration parameters 6 Communication objects 8 AZ6 R...

Page 3: ...will be subject to such purposes and measures as are laid down in environmental protection legislation GENERAL REQUIREMENTS Strictly follow the directions outlined in this manual This system must be i...

Page 4: ...e automation bus of the main control board and the KNX bus of the installation It should be placed and mounted in accordance with the current electrotechnical regulations Note To remove the module pul...

Page 5: ...tally compatible with KNX so you can configure it and set it up through ETS tool To do this download the product database at http doc airzone es producto actuales Airzone Comunes Softwares BBDD_AZX6KN...

Page 6: ...control the AC system through KNX it is necessary to select the proper system topology because this parameter affects the rest of parameters as the number of available zones or the selection of some c...

Page 7: ...vate deactivate the zones from the zone menu When a zone is enabled an Airzone thermostat appears next to the zone menu The value by default is No The default communication objects of the zones are CZ...

Page 8: ...or Type of access to the Bus Reading Data point identification 1 005 DPT_Alarm Object number 1 Name AC operation mode Function Mode changeover Description This object allows the user to change the ope...

Page 9: ...ype of access to the Bus Writing Data point identification 1 001 Object number 5 Name COOLING mode Function On off Description This communication object reads the operation mode status of the AC unit...

Page 10: ...Off On Heating air mode On Type of access to the Bus Writing Data point identification 1 001 Object number 9 Name VENTILATION mode Function On off Description This communication object reads the opera...

Page 11: ...when the mode value is OFF This mode can be only activated when it is available in the AC unit to which the system is connected Values Off Dry mode Off On Dry mode On Type of access to the Bus Writin...

Page 12: ...he month 1 31 Month 1 12 Year 1990 2089 Type of access to the Bus Writing Data point identification 11 001 Object number 17 Name Time Function Time Description This object is used to read the time sto...

Page 13: ...on direct expansion units Values 0 Deactivated 1 Activated Type of bus access Reading Data point identification 1 003 DPT_Enable Object number 21 Name AIR demand Function Status Description This objec...

Page 14: ...zone Values 0 Zone OFF 1 Zone ON Type of bus access Reading Data point identification 1 001 Z 1 Z 2 Z 3 Z 4 Z 5 Z 6 Z 7 Z 8 Z 9 Z 10 Z 11 Z 12 Z 13 Z 14 Object number 25 41 57 73 89 105 121 137 153 1...

Page 15: ...ation 9 007 Z 1 Z 2 Z 3 Z 4 Z 5 Z 6 Z 7 Z 8 Z 9 Z 10 Z 11 Z 12 Z 13 Z 14 Object number 29 45 61 77 93 109 125 141 157 173 189 205 221 237 Name Zone X Local temperature Function Temperature Description...

Page 16: ...ne in 2 pipe 4 pipe or mixed installations with Fancoil local module Values 0 Fan Speed Auto 1 33 Fan Speed 34 66 2 Fan Speed 2 67 100 Fan Speed 3 Type of bus access Writing Data point identification...

Page 17: ...one X Heat Stage Function Configuration Description It is used to change the configuration of the heating stages of the zone Air Underfloor Heating or both of them at the same time Values 1 Air heatin...

Page 18: ...Zone X Cool Stage Function Configuration Description It is used to change the configuration of the cooling stages of the zone Air Underfloor Cooling or both of them at the same time Values 3 Air cooli...

Page 19: ...400 446 http www myzone airzone es Parc Tertiaire Silic Inmeuble Panama 45 Rue Villeneuve 94573 Rungis France T l phone 33 184 884 695 Fax 33 144 042 114 http www myzone airzonefrance fr Via Fabio Fi...

Reviews: