24
ES
EN
FR
IT
PT
DE
EASYZONE ASSEMBLY
Important:
It is recommended to insulate all the metal parts of Easyzone that are exposed to outdoor conditions in order to
prevent condensation.
Remember:
The motorized elements are numbered the following way:
ASSEMBLY TO INDOOR UNIT
Locate the fixing holes. If they are covered, use a screwdriver to uncover them in order to assemble the Easyzone in the
unit.
Important:
If your unit has circular adapters in the front part, remove it and mount the adapter to Easyzone provided by Airzone.
Place the Easyzone in the pressure port of the unit and attach it to this using the screws.
After fixing screws be sure to insulate the connection frame to prevent condensation forming. Use bands of insulating
material (glass wool or polyethylene foam) of a thickness of 25 mm. The width of the insulation bands are 97 mm for standard
motorized plenum and 36 mm for low profile motorized plenum.
Attach the Easyzone to the ceiling through the tabs on the ends with threaded rods.
Summary of Contents for AZZS6AERST
Page 2: ......
Page 30: ...30 ES EN FR IT PT DE Think Important Use to confirm and to return...
Page 111: ......