1.- Thermostat connection
If using a wired thermostat, connect it in one of the 3 Airzone connection bus terminals.
The connection can be both a Bus connection or a star connection. Use (2x0.5+2x0.22
mm
2
) Airzone wire. For added security, secure the wires using the turrets.
In case of wireless element, check it has the battery on.
2.- Connection to the ducted unit
In order to connect it to ducted unit,
follow the instructions of the communication gateway sheet
. It is recommended to
install the thermostat of the unit.
3.- Other peripherals (AZCE6OUTPUT8, AZX6CCP, AZX6WEBSCLOUD [C/R], …)
You can find the instructions on how to connect and configure other peripherals on their data sheets.
Important:
For elements externally powered at 110/230 Vac, for their communications, it is only necessary to connect the poles
"A" and "B" of the bus.
4.- Powering the system
Use the power input to power at 110 / 230 Vac
the main control board and any others
control elements that require it. Use the appropriate cable (3x1.5 mm²). To power supply
the Main Board of the system, loosen the cable gland if necessary and insert the cable
through the hole (Ø: 5-10 mm), attach the cables with the terminal following the indicated
polarity. Connect the terminal to the power supply input and tighten the cable gland to
attach the power supply cable.
According to the current local and national regulations, it is mandatory to add a switch (or other element
to disconnect the system) to the external supply wiring so that a constant separation between poles is
guaranteed. The system will restart automatically if the supply is eventually turned off.
Use an
independent circuit from the controlled system for the power supply.
Remember:
Once all the connections are made, make sure you replace the cover properly.