From this menu you can change the system and zone parameters.
SYSTEM PARAMETERS
•
System address
(not available on systems with BACnet gateway)
.
Use this parameter to define the system number in
your installation using this parameter. The
Supermaster
option
(available in installations with Airzone production
control board, AZX6CCP)
.
Allows you to impose the operation mode of the system to the rest of the systems connected
to the AZX6CCP in a semi-forced way.
•
Temperature range.
Use this parameter to select the highest temperature in heating mode (19-30 ºC, by default 30ºC)
and the lowest temperature in cooling mode (18-26 ºC, by default 18ºC). It is also possible to disable some of the
modes.
•
Combined stage
(only available in installations with AZCE6OUTPUT8 modules)
. Enables activating and deactivating the
combined stage of the “Control Stages” parameter in the user’s Zone Settings Menu.
•
Hysteresis Configuration.
Defines the temperature differential between the room temperature and the set-point
temperature required to start applying the Algorithm RadianT.
This algorithm prevents overheating in underfloor air
conditioning installations. If your installation has radiators, set this value to 0ºC. (By default 0ºC)
•
Type of opening.
Use this parameter to configure the type of opening of the damper output. (By default All/Nothing).
*Note:
If you change this parameter, all the dampers of the installation will be affected. It is not recommended for RINT and
RIC intelligent grilles.
•
Standby mode
(only for Blueface thermostats)
. Configuration of the operating logic of the motorized elements when
there is no demand on the system. This is dabled by default.
•
Relay settings.
Use this parameter to change the operation logic of the CMV/Boiler of the system main control board.
(By default CMV).
•
Return temperature
(only available for installations with AZX6SONDPROTEC)
.
Defines the cut-off temperatures of the
system for both heating (32ºC, 34ºC and 36ºC) and cooling mode (6ºC, 8ºC and 10ºC) in order to protect the AC unit. It
is set by default in 34ºC in heating mode and 8ºC in cooling mode.
•
Q-Adapt
(only for Think thermostats)
.
-
Direct expansion units.
Select the control algorithm that best fits your installation. These are the available
options:
-
Maximum: the system operates at maximum speed, irrespective of the number of zones.
-
Power: the speed of the system is higher than in standard mode to increase the flow.
-
Standard (by default): the system automatically regulates the speed based on the number of zones.
-
Silence: the speed of the system is lower than in standard mode to reduce the noise.
-
Minimum: the system operates at minimum speed, irrespective of the number of zones.
-
0-10 V Fancoil units.
Allows to control the minimum (1.5 V by default) and maximum (10 V by default) working
fan voltage of the controlled unit, in steps of 0.1 V. The minimum voltage corresponds with the desired lowest
Operation mode:
System 1
Available operation modes:
Rest of the systems