12
GENERAL REQUIREMENTS
Strictly follow the directions outlined in this manual:
•
This system must be installed by a qualified technician.
•
Verify that the units to be controlled have been installed according to the manufacturer's requirements and operate
correctly before installing the Airzone System.
•
Locate and connect all the devices of the installation in accordance with the electronic regulations in force.
•
Verify that the air conditioning installation to be controlled is in accordance with the regulations in force.
•
To install the flexible duct, follow the local recommendations for its ubication and isolation of the ducts to the damper.
Perform a cut along the isolated area to maintain the actuator of the damper outside it. Once finished, check the
tightness of the joints between the damper and the duct.
•
On zones controlled by wireless controllers, place the dampers and zone modules as close as possible to the wireless
controller of the zone.
•
Follow these recommendations to locate the controllers:
•
Make all the connection with total absence of power supply.
•
In order to connect the elements of the system, use only Airzone 4 wires cable: 2x0.22 mm2 shielded twisted wires for
data communication and 2x0.5 mm2 for power supply.
The connection between the control modules must be
made in Bus mode.
•
Do not place the system bus close to lines of force, fluorescent lights, LED lamps, motors, etc. It might cause
interference on the communications.
•
Respect the connection polarity of each device. A wrong connection may seriously damage the product.