18
WIRED/WIRELESS INTELLIGENT ROUND DAMPER (AZVAFDAMPERXX [C/R])
Assembly
Connection
The Intelligent round damper is connected to the Airzone Connection Bus of the control board (Fig. 11).
It has a 5-pin terminal to connect it to the Airzone Connection Bus of the main board. Use the proper
cable: shielded twisted pair 4 wired: 2x0.22 mm
2 +
2x0.5mm
2
(AWG 20 – 4 wired). Attach the wires with the
terminal screws following the color code (Fig. 12).
It has a 4-pin terminal to connect the controller. Use the proper cable: shielded twisted pair 4 wired: 2x0.22
mm
2 +
2x0.5mm
2
(AWG 20 – 4 wired). Attach the wires with the terminal screws following the color code
(Fig. 13).
Remember:
The maximum separation between the module and the controller is 10 meters.
The zoning module allows you to connect a probe (AZVAF10KPROBE) for remote or distributed temperature reading,
depending on how the module is configured:
WIRELESS OPTION
Place the dampers as close as possible to the wireless controller of the zone.
Fig. 10
N˚
Meaning
Motorized element connector
Probe connector
Airzone Connection Bus
Controller connection
(Only AZVAFDAMPERxxC)
Presence contact
Window contact
Note:
Use a shielded twisted pair to connect the window contact.
Fig. 11
Fig. 12