37
Main ID of the Lite controller
In case there are more than one master controller on the installation, It is required to set the Main ID parameter of the Lite
Controller for its proper functioning
(see section
Advanced settings – Blueface controller
). If no master is configured
for the Lite controller, the error "Lite without Main ID" will be displayed on the Blueface controller while all Lite LEDs
will show a steady white light.
Configure other functionalities of the LITE controller from the advanced configuration menu of a Blueface controller (see
section
) or Webserver Cloud (See Webserver Cloud installation manual).
IMPORTANT:
For changing the zone ID, access the parameter Zone ID,
inside the advanced settings menu from a Blueface
controller
Lite controller reset
To reset to factory values on any Lite controller, remove the Lite controller from its base, turn up the microswitch 8 and place it
again on its base. Press on
, the LED will flash blink twice when the reset process is completed.
To reassociate it, lower the microswitch 8, place the controller on its base and follow the steps displayed in the
INITITAL CONFIGURATION EVALUATION
Check the following aspects:
-
AC unit-system communication: Choose any mode (except for STOP mode) and switch on the zone to generate
demand. Verify that the selected operation mode in the Main controller is shown in the indoor unit controller and the
set-point temperature changes.
-
Opening-closing of the dampers, ON/OFF of individual AC units and control outputs: Turn on the system and generate
demand in all the zones. Then, switch off and on each zone to verify the element to be controlled operates properly.
-
Verify that the static pressure of the duct system complies with the air distribution network conditions where is
installed (check the Manufacturer’s Manual of the equipment if you need to modify this parameter).
Important:
After the setup or in case of power outage, the system takes a few minutes to measure precisely the temperature
and the relative humidity.