53
Error 17: Communication error between Lutron Integration Gateway – System
The system loses communication with the Airzone Lutron Interface. Check that the gateway is properly connected to the
automation bus of the Main Board.
AC unit error: Error in the AC unit
Check the type of error in the AC unit controller and follow the instructions provided by the manufacturer.
LITE CONTROLLERS (AZVAFLITE [C/R])
Lite controllers incorporate LEDs that detect malfunctioning.
Status LED
blinking purple quickly: Wired Lite Controller- Zone module communication error (AZVAFDAMPERxxC
/ AZVAFZMRADC / AZVAFZMOxxxC)
This incident blocks the control of the zone. To solve this incident check:
1.
Connection: Check the polarity of the connectors of the module and the controller.
2.
Wiring: Check that the voltage between the poles (A /-) and (B/-) is about 0.65 Vdc.
3.
Wiring: Verify that the module connection bus-controller is not next to low-voltage wiring.
4.
Module: Check the correct operation of the module, for this connect another controller and verify that Error 1 does not
appear on the screen.
5.
Restart the zone and re-associate it with the system.
Remember:
To reset to factory values of any Lite controller, turn up the microswitch 8 and place the controller on the base
again. Press on
, the LED will flash green twice when the reset process is completed.
6.
Restart system: If the system is restarted, this error may be displayed in the controllers at the beginning of the process.
This message should disappear after around 30 seconds.