Heating stage.
(Only available if have air and radiant stages enabled in a zone,
see zone parameters/Control stages
This option configures the following parameters of the Air+Radiant control stage:
-
Temperature gap. Defines the temperature gap after which the second stage must be activated.
-
First stage. Defines the first stage to operate: Air or Radiant.
•
BACnet.
This parameter displays the Device ID, the uplink port, the IP address, the subnet mask and the Gateway IP
and allows you to modify them. Press on the value you want to change, modify it and then press to confirm. The values
by default are:
-
Device ID: 1000
-
Port: 47808
-
IP Address: DHCP
•
Supply temperature
(only available in installations with Airzone VAF 10 KOhm NTC thermistor).
This option allows the
system demand to be ignored if the supply temperature exceeds a certain limit. The selectable heating cut out
temperatures are 38-46-54-62-70˚C / 100-114-129-143-158˚F. By default, the system will stop heating if the supply
temperature reaches 54˚C / 129˚F.
Note:
The system will not generate heat until past 4 minutes (minimum) from the shut of demand.
•
Air supply setting
.
(Only available in Blueface controller if radiant control stage has been enabled as Air supply in at least
one zone; see Zone settings/Control stages)
. This allows you to choose the type of auxiliary unit that provides air supply
support, as well as the delay applied to the fan:
-
Electric.
Electrical unit that generates heat assisted by the indoor AC unit's fan. The fan start delay time is fixed
(90 seconds) and cannot be configured. This allows you to configure the
Fan delay Off (s)
parameter to set the
fan off delay time to ensure proper heat dissipation. This is set to 0 seconds by default.
-
Water.
Water unit that generates heat assisted by the indoor AC unit's fan. This allows you to configure the
Fan
delay On/Off (s)
parameter to set the fan start and stop delay time to ensure that the working temperature is
reached before starting to ventilate and to ensure correct heat dissipation when the demand for air supply
support ceases.
•
Internet connection.
(Only available for Blueface controller)
It Enables/disables the internet connection of the system.
•
Room temperature.
This option allows the room temperature and relative humidity to be shown/hidden. By default,
the room temperature is shown.
•
Radio channel.
It activates/deactivates the radio channel of the system.
•
Reset system
(only available for main controller)
.
Resets the system and returns to factory settings. To reconfigure the
controllers, please check
Zone settings
•
Zone ID
(only available from remote zones, in zones controlled by Lite controllers)
. Shows and allows to modify the zone
number assigned among the availables.
Important:
It is necessary to set the Main ID parameter of the controller for its proper functioning.
•
Linked zones.
It displays and allows you to select the control outputs associated with the controller.
•
Controller settings.
Use this parameter to define the controller as Main or Zone.
•
Main ID
(only available if the controller is configured as zone)
.
Sets the main zone, which imposes its mode to this zone
(only set-point temperature and fan speed features will be configurable).
•
Use mode.
The controllers can be set in Basic or Advanced mode. They are set in Advanced mode by default. These
are the parameters you can control in basic mode: On/off, set-point temperature, airflow/fan speed and operation
mode. If you need to reset the controller to Advanced mode, access the advanced configuration menu and then
activate the advanced use mode.
•
Offset.
Correction factor for the room temperature of the zones (range: from -2.5˚C to 2.5 ˚C / -5˚F to 5˚F in steps of
0.5˚C / 1˚F). It is in 0˚C / 0˚F by default.