For changing the zone address, access the parameter Zone ID,
inside the advanced settings menu from a
Blueface thermostat
(see section
Advanced settings
,
Zone settings
).
Lite thermostat reset
To reset to factory values of any Lite thermostat, turn up the microswitch 8 and place the thermostat on the base again. Press
on
, the LED will flash green twice when the reset process is completed.
INITIAL CONFIGURATION EVALUATION
Check the following aspects:
-
AC unit-system communication: Choose any mode (except for STOP mode) and switch on the zone to generate
demand. Verify that the selected operation mode in the Main thermostat is shown in the indoor unit thermostat and
the set-point temperature changes.
-
Opening-closing of the dampers, ON/OFF of individual AC units and control outputs: Turn on the system and generate
demand in all the zones. Then, switch off and on each zone to verify the element to be controlled operates properly.
-
Verify that the static pressure of the duct system complies with the air distribution network conditions where is
installed (check the Manufacturer’s Manual of the equipment if you need to modify this parameter).
Important:
After the setup or in case of power outage, the system takes a few minutes to measure precisely the temperature
and the relative humidity.
FLOW REGULATION
If necessary, set the flow adjustment and minimum air of the system dampers:
FLOW ADJUSTMENT (REG)
1.
Turn on and generate demand in all zones to open all the dampers.
2.
Turn off the zone/damper to be adjusted.
3.
Adjust the maximum opening you want with the REG lever (I/II/III/IV).
4.
Turn on the zone and check the flow is correct.
MINIMUM AIR SETTING (A-M)
1.
Turn on and generate demand in all zones to open all the dampers.
2.
Adjust the minimum opening you want with the M-A lever (a/b/c/d).
3.
Turn on the zone and check the minimum air flow is correct.
A-M
REG