Reset thermostat
(not available in remote zones)
.
Allows you to reset the thermostat and returning it to the default
values.
ADVANCED SETTINGS – THINK THERMOSTAT
To access the advanced configuration menu, follow the next steps:
Important:
In Think thermostats, press
to confirm and
to return to the previous menu/screen.
Linked zones.
It displays and allows you to select the control outputs associated with the thermostat.
Thermostat settings.
Use this parameter to define the thermostat as Main or Zone.
Main ID
(only available if the thermostat is configured as zone)
.
Sets the main zone, which imposes its mode to this zone
(only set-point temperature and fan speed features will be configurable).
Use mode.
The thermostats can be set in Basic or Advanced mode. They are set in Advanced mode by default. These
are the parameters you can control in basic mode: On/off, set-point temperature, airflow/fan speed and operation
mode.
If you need to reset the thermostat to Advanced mode, access the advanced configuration menu and then activate
the advanced use mode.
Offset.
Correction factor for the room temperature of the zones (range: from -2.5˚C to 2.5 ˚C / -5˚F to 5˚F in steps of
0.5˚C / 1˚F). It is in 0˚C / 0˚F by default.
Control stages.
This parameter is used to select cooling/heating stages in the zone. These are the features to be
configured:
-
Air: It activates the heating air in the zone.
-
Radiant:
It activates radiant heating.
-
Air+Radiant: It activates both air and radiant heating in the zone and also allows the user to select the desired
heating stage: Air, Radiant or Air+Radiant.
-
Off: It deactivates the cooling/heating stage in the zone.
Occupancy contact.
It determines the state of the module of a zone based on the occupancy. It only has effect on the
zone module if it is associated to a thermostat (it does not operate in secondary zone modules). When this contact is
on, if the zone is empty for over 5 minutes, the Sleep 90 feature is activated (displaying an Occupancy notification on
the thermostat). It is off by default. In order to activate this feature, configure it as Normally open or Normally closed.
Window contact.
This option allows the control the state of a zone module based on the opening of the window. It
only has effect on the control element of the zone module. When this contact is on, if it detects any open window, it
turns off the zone after 60 seconds (displaying an Open window notification on the thermostat). It is off by default. In
order to activate this feature, configure it as Normally open or Normally closed.
Weight.
This option is used to set the weight of each zone for purposes of determining system operation. The weight
of the zone will be used for calculating the mode (auto-change over) or for calculating heat demands when using
auxiliary heat. It is an indicator of the size / importance of the zone. Possible values range from 0-100. By default, the
weighting is set to Auto and each zone's weight is automatically generated based on the number of zones. For
Press once
Press and hold
Press and hold