1575H031 Ed.01
Data printing (Only AKO-15742, 15752 and 15782)
Fast printing
When the logger is in any of the display modes, pressing the
D
key makes the device print the graphs of all the
active inputs, with the data logged in the last closed log block.
The data contained in each log block depend on the “log interval” parameter, as shown in the table:
If the parameter “Log start day” is set at “Monday” and the “Log interval” is set at “15 min.” (default
configuration), the log block starts on Monday at 00:00 and closes on Sunday at 23:59.
Selective printing
When the logger is displaying the data for a specific date and input (“Graph”, “List” or “Histogram” display
modes), when the
D
key is pressed, the device prints the data displayed on the screen.
When the logger is displaying the configuration change log or alarm log, when the
D
key is pressed, the device
prints the data displayed on the screen.
Connectivity
CAMRegis loggers have a port for connection of RS485 (MODBUS) data, that allow remotely managing them using
a PC with the
SOFTRegis
,
AKONet
software or an
AKO-5011
server.
A different address must be assigned for each device in the same network, this address is defined using the
Configuration - Modbus Address parameter.
Recommended cable:
AKO-15586
Log interval
Period to be printed
5 min.
24 hours
15 min.
Last complete week
30 min.
14 days
ESC
?
SET
ESC
?
SET
21
13
13
21
xx
xx
22
14
14
22
xx
xx
23
15
15
23
xx
xx
CAM
Regis
AKO-157
xx
AKO controllers
with communication
CAM
Ctrl
AKO-156
xx
AKO-80039
PC +
AKONet
Tr-
Gnd
Tr+
AKO-5011
LAN
Data printing (Only AKO-15742, 15752 and 15782)
Fast printing
When the logger is in any of the display modes, pressing the
D
key makes the device print the graphs of all the
active inputs, with the data logged in the last closed log block.
The data contained in each log block depend on the “log interval” parameter, as shown in the table:
If the parameter “Log start day” is set at “Monday” and the “Log interval” is set at “15 min.” (default
configuration), the log block starts on Monday at 00:00 and closes on Sunday at 23:59.
Selective printing
When the logger is displaying the data for a specific date and input (“Graph”, “List” or “Histogram” display
modes), when the
D
key is pressed, the device prints the data displayed on the screen.
When the logger is displaying the configuration change log or alarm log, when the
D
key is pressed, the device
prints the data displayed on the screen.
Connectivity
CAMRegis loggers have a port for connection of RS485 (MODBUS) data, that allow remotely managing them using
a PC with the
SOFTRegis
,
AKONet
software or an
AKO-5011
server.
A different address must be assigned for each device in the same network, this address is defined using the
Configuration - Modbus Address parameter.
Recommended cable:
AKO-15586
Data printing (Only AKO-15742, 15752 and 15782)
Fast printing
When the logger is in any of the display modes, pressing the
D
key makes the device print the graphs of all the
active inputs, with the data logged in the last closed log block.
The data contained in each log block depend on the “log interval” parameter, as shown in the table:
If the parameter “Log start day” is set at “Monday” and the “Log interval” is set at “15 min.” (default
configuration), the log block starts on Monday at 00:00 and closes on Sunday at 23:59.
Selective printing
When the logger is displaying the data for a specific date and input (“Graph”, “List” or “Histogram” display
modes), when the
D
key is pressed, the device prints the data displayed on the screen.
When the logger is displaying the configuration change log or alarm log, when the
D
key is pressed, the device
prints the data displayed on the screen.
Connectivity
CAMRegis loggers have a port for connection of RS485 (MODBUS) data, that allow remotely managing them using
a PC with the
SOFTRegis
,
AKONet
software or an
AKO-5011
server.
A different address must be assigned for each device in the same network, this address is defined using the
Configuration - Modbus Address parameter.
Recommended cable:
AKO-15586
Data printing (Only AKO-15742, 15752 and 15782)
Fast printing
When the logger is in any of the display modes, pressing the
D
key makes the device print the graphs of all the
active inputs, with the data logged in the last closed log block.
The data contained in each log block depend on the “log interval” parameter, as shown in the table:
If the parameter “Log start day” is set at “Monday” and the “Log interval” is set at “15 min.” (default
configuration), the log block starts on Monday at 00:00 and closes on Sunday at 23:59.
Selective printing
When the logger is displaying the data for a specific date and input (“Graph”, “List” or “Histogram” display
modes), when the
D
key is pressed, the device prints the data displayed on the screen.
When the logger is displaying the configuration change log or alarm log, when the
D
key is pressed, the device
prints the data displayed on the screen.
Connectivity
CAMRegis loggers have a port for connection of RS485 (MODBUS) data, that allow remotely managing them using
a PC with the
SOFTRegis
,
AKONet
software or an
AKO-5011
server.
A different address must be assigned for each device in the same network, this address is defined using the
Configuration - Modbus Address parameter.
Recommended cable:
AKO-15586
Data printing (Only AKO-15742, 15752 and 15782)
Fast printing
When the logger is in any of the display modes, pressing the
D
key makes the device print the graphs of all the
active inputs, with the data logged in the last closed log block.
The data contained in each log block depend on the “log interval” parameter, as shown in the table:
If the parameter “Log start day” is set at “Monday” and the “Log interval” is set at “15 min.” (default
configuration), the log block starts on Monday at 00:00 and closes on Sunday at 23:59.
Selective printing
When the logger is displaying the data for a specific date and input (“Graph”, “List” or “Histogram” display
modes), when the
D
key is pressed, the device prints the data displayed on the screen.
When the logger is displaying the configuration change log or alarm log, when the
D
key is pressed, the device
prints the data displayed on the screen.
Connectivity
CAMRegis loggers have a port for connection of RS485 (MODBUS) data, that allow remotely managing them using
a PC with the
SOFTRegis
,
AKONet
software or an
AKO-5011
server.
A different address must be assigned for each device in the same network, this address is defined using the
Configuration - Modbus Address parameter.
Recommended cable:
AKO-15586
Data printing (Only AKO-15742, 15752 and 15782)
Fast printing
When the logger is in any of the display modes, pressing the
D
key makes the device print the graphs of all the
active inputs, with the data logged in the last closed log block.
The data contained in each log block depend on the “log interval” parameter, as shown in the table:
If the parameter “Log start day” is set at “Monday” and the “Log interval” is set at “15 min.” (default
configuration), the log block starts on Monday at 00:00 and closes on Sunday at 23:59.
Selective printing
When the logger is displaying the data for a specific date and input (“Graph”, “List” or “Histogram” display
modes), when the
D
key is pressed, the device prints the data displayed on the screen.
When the logger is displaying the configuration change log or alarm log, when the
D
key is pressed, the device
prints the data displayed on the screen.
Connectivity
CAMRegis loggers have a port for connection of RS485 (MODBUS) data, that allow remotely managing them using
a PC with the
SOFTRegis
,
AKONet
software or an
AKO-5011
server.
A different address must be assigned for each device in the same network, this address is defined using the
Configuration - Modbus Address parameter.
Recommended cable:
AKO-15586
Data printing (Only AKO-15742, 15752 and 15782)
Fast printing
When the logger is in any of the display modes, pressing the
D
key makes the device print the graphs of all the
active inputs, with the data logged in the last closed log block.
The data contained in each log block depend on the “log interval” parameter, as shown in the table:
If the parameter “Log start day” is set at “Monday” and the “Log interval” is set at “15 min.” (default
configuration), the log block starts on Monday at 00:00 and closes on Sunday at 23:59.
Selective printing
When the logger is displaying the data for a specific date and input (“Graph”, “List” or “Histogram” display
modes), when the
D
key is pressed, the device prints the data displayed on the screen.
When the logger is displaying the configuration change log or alarm log, when the
D
key is pressed, the device
prints the data displayed on the screen.
Connectivity
CAMRegis loggers have a port for connection of RS485 (MODBUS) data, that allow remotely managing them using
a PC with the
SOFTRegis
,
AKONet
software or an
AKO-5011
server.
A different address must be assigned for each device in the same network, this address is defined using the
Configuration - Modbus Address parameter.
Recommended cable:
AKO-15586
+
R
S-
4
8
5
GND
Data printing (Only AKO-15742, 15752 and 15782)
Fast printing
When the logger is in any of the display modes, pressing the
D
key makes the device print the graphs of all the
active inputs, with the data logged in the last closed log block.
The data contained in each log block depend on the “log interval” parameter, as shown in the table:
If the parameter “Log start day” is set at “Monday” and the “Log interval” is set at “15 min.” (default
configuration), the log block starts on Monday at 00:00 and closes on Sunday at 23:59.
Selective printing
When the logger is displaying the data for a specific date and input (“Graph”, “List” or “Histogram” display
modes), when the
D
key is pressed, the device prints the data displayed on the screen.
When the logger is displaying the configuration change log or alarm log, when the
D
key is pressed, the device
prints the data displayed on the screen.
Connectivity
CAMRegis loggers have a port for connection of RS485 (MODBUS) data, that allow remotely managing them using
a PC with the
SOFTRegis
,
AKONet
software or an
AKO-5011
server.
A different address must be assigned for each device in the same network, this address is defined using the
Configuration - Modbus Address parameter.
Recommended cable:
AKO-15586
Data printing (Only AKO-15742, 15752 and 15782)
Fast printing
When the logger is in any of the display modes, pressing the
D
key makes the device print the graphs of all the
active inputs, with the data logged in the last closed log block.
The data contained in each log block depend on the “log interval” parameter, as shown in the table:
If the parameter “Log start day” is set at “Monday” and the “Log interval” is set at “15 min.” (default
configuration), the log block starts on Monday at 00:00 and closes on Sunday at 23:59.
Selective printing
When the logger is displaying the data for a specific date and input (“Graph”, “List” or “Histogram” display
modes), when the
D
key is pressed, the device prints the data displayed on the screen.
When the logger is displaying the configuration change log or alarm log, when the
D
key is pressed, the device
prints the data displayed on the screen.
Connectivity
CAMRegis loggers have a port for connection of RS485 (MODBUS) data, that allow remotely managing them using
a PC with the
SOFTRegis
,
AKONet
software or an
AKO-5011
server.
A different address must be assigned for each device in the same network, this address is defined using the
Configuration - Modbus Address parameter.
Recommended cable:
AKO-15586
English