1662H411 Ed.06
20
20
Description
Values Min.
Def.
Max.
Re
C40
Frequency of air extraction cycles (time between starts)
(Only if
o80
or
o81
=1) (0=Only keypad activation)
h.
0
0
24
C41
Duration of air extraction cycles (
0
=deactivated)
Min.
0
0
600
EP
Exit to level 1
Description
Values Min.
Def.
Max.
RX
SPX
Moisture setting (Moisture set point)
% HR
30
85
100
rX00
Moisture probe calibration (Offset)
% HR
-10
0
10
rX01
Moisture probe differential (Hysteresis)
% HR
0.5
5
10
rX02
Upper locking of SPH (it cannot be set above this value)
% HR
rH03
100
100
rX03
Lower locking of SPH (it cannot be set below this value)
% HR
30
30
rH02
rX04
Humidifier active during defrost
0
= No
1
=Yes
0
0
1
rX05
Maximum time for dehumidifier to be ON. From this value onwards, cold is
activated to reduce moisture (
0
=Cold is not activated for this function)
Min.
0
0
240
rX06
Maximum time for heat provision via hot gas until resistors are activated.
Min.
0
0
240
EP
Exit to level 1
Temperature regulation and control
Moisture regulation and control
* According to wizard.
It can only be modified using the configuration wizard (In1/2).
†
Description
Values Min.
Def.
Max.
DEF
d0
Defrost frequency (Time between 2 starts)
H.
0
6
96
d1
Maximum defrost duration (
0
=defrost deactivated)
Min.
0
60
255
d2
Type of message during the defrost:
0
=Displays the real temperature;
1
=Displays the temperature at the start of the
defrost;
2
=Displays the dEF message
0
2
2
d3
Maximum duration of the message
(Time added at the end of the defrost process)
Min.
0
5
255
d4
Final defrost temperature (via probe 2,
l00
=2)
ºC/ºF
-50
8.0
C2
d5
Defrost on connecting the unit:
0
=NO First defrost according to d0;
1
=YES, First defrost according to d6
0
0
1
d6
Delay of the defrost start on connecting the unit
Min.
0
0
255
d7
Type of defrost:
0
=Resistors;
1
=Air/fans
2
=Deactivated
0
*
3
d8
Count of time between defrost periods:
0
=Total real time
1
=Sum of compressor connected time
0
0
1
d9
Drip time when completing defrost (Shutdown of compressor and fans)
Min.
0
1
255
EP
Exit to level 1
Level 1
Level 2
Defrost
†
Level 1
Level 2
Level 1
Level 2