1662H411 Ed.06
21
21
* According to wizard.
English
Description
Values Min.
Def.
Max.
fAN
F0
Fan stop temperature via probe 2
ºC/ºF
-50
45
50
F1
Probe 2 differential (Hysteresis)
ºC/ºF
0.1
2.0
20.0
F2
Shut down fans when the compressor shuts down
0
=No
1
=Yes
0
0
1
F3
Status of the fans during the defrost
0
=Shut down;
1
=Running
0
*
1
F4
Delay of start-up after defrost (If F3=0)
It will only actuate if it is higher than
d9
Min.
0
2
99
F10
Maximum time permitted for fans to be off.
(Anti-stratification function) (
0
=Disabled)
Min.
0
0
360
F11
Duration of anti-stratification function
Sec.
0
0
900
EP
Exit to level 1
Level 1
Level 2
Evaporator fans
Description
Values Min.
Def.
Max.
AL
A0
Configuration of the temperature alarms
0
=Relative to SP
1
=Absolute
0
1
1
A1
Maximum temperature alarm in probe 1 (it must be higher than the SPt)
ºC/ºF
A2
20
99
A2
Minimum temperature alarm in probe 1 (it must be lower than the SPt)
ºC/ºF
-50
-50
A1
A3
Delay of temperature and moisture alarms during start-up
Min.
0
0
120
A4
Delay of temperature and moisture alarms after the end of a defrost
Min.
0
0
99
A5
Delay of temperature alarms from when the
A1
or
A2
value is reached
0
30
99
A6
Delay of the external alarm/Severe external alarm on receiving a signal in digital
input (
I10
or
I20
=2 or 3)
Min.
0
0
120
A7
Delay of external alarm deactivation/Severe external alarm deactivation when the
signal in digital input disappears (
I10
or
I20
=2 or 3)
Min.
0
0
120
A8
Show warning if the defrost ends for maximum time
0
=No
1
=Yes
0
0
1
A9
Relay alarm polarity
0
= Relay ON in alarm (OFF without alarm);
1
= Relay OFF in alarm (ON without alarm)
0
0
1
A10
Differential of temperature alarms (
A1
and
A2
)
ºC/ºF
0.1
1.0
20.0
A12
Delay of open door alarm (If
I10
or
I20
=1)
Min.
0
10
120
A20
Configuration of moisture alarms
0
=Relative to SP
1
=Absolute
0
0
1
A21
Maximum moisture alarm (it must be higher than the SPH)
% HR
A22
20
100
A22
Minimum moisture alarm (it must be lower than the SPH)
% HR
-50
-40
A21
A23
Differential of moisture alarms (
A21
and
A22
)
% HR
0.1
2
20
A24
Delay of moisture alarms from when
A21
or
A22
are reached
Min.
0
30
99
EP
Exit to level 1
Level 1
Level 2
Alarms