1662H411 Ed.06
24
24
Description
Values Min.
Def.
Max.
TiD
In1
Option chosen in the In1 configuration wizard
In2
Option chosen in the In2 configuration wizard
Pd
Pump down active?
0
=No
1
=Yes
0
*
1
PU
Programme version
Pr
Programme revision
bU
Bootloader version
br
Bootloader revision
pAr
Parameter map revision
EP
Exit to level 1
Level 1
Level 2
Information (Reading only)
†
* According to wizard.
It can only be modified using the configuration wizard (In1/2).
†
A:
Activates the acoustic alarm
R:
Activates the alarm relay (If
o10
=1)
Messages
MESSAGES
DESCRIPTION
A
R
Pd
Pump down malfunction error (Shutdown)
LP
Pump down malfunction error (Start-up)
E1
/
E2
/
E3
Probe 1/2/3 failure (Open circuit, crossed circuit or temperature outside the limits of the probe)
(Equivalent limits in °F)
•
•
EX
Moisture probe failure (Open circuit, crossed circuit or values beyond probe limits)
•
•
Ad0
Open door alarm. Only if the door stays open for a greater time than is indicated in parameter
A12
•
•
AK
Maximum temperature alarm in control probe. The temperature value programmed in
A1
has been
reached
•
•
AL
Minimum temperature alarm in control probe. The temperature value programmed in
A2
has been
reached
•
•
AE
External alarm activated (by digital input)
•
•
AES
Severe external alarm activated (by digital input)
•
•
Adt
Defrost alarm concluded due to time-out. The time established in
d1
has been exceeded
KCP
HACCP alarm. The temperature has reached the value of parameter
h1
during a longer period than has
been established in
h2
•
•
HCP
+
PF
HACCP alarm due to a fault in the electric supply. The temperature established in
h1
has been reached
following a fault in the electric supply
•
•
DEF
Indicates that a defrost is being performed
PAS
Access code (Password) request. See parameters
b01
and
PAS
AXX
Maximum moisture alarm in moisture probe. The temperature value programmed in
A21
has been
reached
•
•
ALX
Minimum moisture alarm in moisture probe. The temperature value programmed in
A22
has been
reached
•
•
Efn
Indicates that the extractor fans are activated.
Summary of Contents for AKO-16624