background image

Trapped person alarm

Quick guide

5542H412 Ed.01

3

5

5

5

4

2

4

1

2   R

ev 0

0  2

0

1

7

AKO ELECTROMECÁNICA , S.A.L.

Avda. Roquetes, 30-38
08812 

 Sant Pere de Ribes.

Barcelona 

 Spain.

Tel.: +34 902 333 145
Fax: +34 938 934 054

www.ako.com

AKO-55424

GB

We reserve the right to supply materials that might vary slightly to those described in 
our Technical Sheets. Updated information is available on our website.

Warnings

-The alarm and push-buttons should be installed in a place protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed the 

value indicated in the technical data. The station should be located in a monitored area, where it is guaranteed that people able to alert to the presence of alarms will 
be present.

-Neither the alarm nor the push-button are suitable for areas classified as potentially explosive.

Wiring

Always disconnect the power supply to carry out wiring.
The wiring between the push-button and the station must 

NEVER

 be installed in a conduit alongside power, control or supply cables.

For disconnection, the power supply circuit must be equipped with a switch of at least 2 A, 230 V, located near the device. The power supply cable will be H05VV-F or NYM 

2

1x16/3. The section to be used will depend on current local regulations, but should never be less than 1.5 mm .
Cables for wiring the relay contact should have the relevant section for the device to be connected.
The 120 / 230 V~ wiring area must be kept clear of any other external element.

Ensure that you have connected the batteries before starting up the device.

Certain international standards indicate that alarm power supply should originate from a different circuit to that used for the refrigeration and ventilation system. 

Be sure 

to comply with current local regulations.

Technical specifications

Power supply.................................................................................100-240 V~ - 50/60 Hz
Maximum input power ..............................................................................................15 W
Accumulators ...............................................................................................Ni-MH 1.6 Ah
Li alarm autonomy.........................................................................> 10 Hours (*)
No. of inputs ...................................................................................................................4
Compatibility of inputs.................................................................AKO-55326 push-button
Alarm relay..........................................................................................SPDT 8(2)A 250 V~
Working ambient temperature......................................................................-5 ºC to 50 ºC

Storage ambient temperature.....................................................................-30 ºC to 60 ºC
Protection degree ......................................................................................................IP 65
Installation category .................................................................................II s/ EN 61010-1
Pollution degree .......................................................................................II s/ EN 61010-1
Double isolation between power supply, secondary circuit and relay output.
Sound power ......................................................................................90 dB(A) at 1 metre
MODBUS address.......................................................................................Shown on label
Maximum push-button cable distance......................................................................300 m
Dimensions .......................................................290 mm (W) x 141 mm (H) x 84.4 mm (D)

AKO-55326

15V

Out

Tr

C

Tr+

 

1

Gnd

2

Trapped

person

RS485

RY1

15V

15V

15V

In

In

In

Gnd

Gnd

Gnd

Input 1

Input

Input 2

15V

15V

In

In

Gnd

Gnd

Input 3

Input 4

Vac

100 - 240 V

~

50/60 Hz

AKO-55424

ALARM

*Duration in alarm status at an ambient temperature of between 25 ºC.