07/2015
Temperature Difference Controller TDC 3
Page 13 of 47
D.5 Solar with 2 zone storage tanks
Actuating direction of valve:
R2 on/valve on = charge to sensor 3
(storage tank above)
D.6 Solar with ext. heat exchanger
Sensor side
max. 12 V
Mains side
230 VAC
Relay R1: For speed control of
standard pumps, minimum load 20 VA
Low voltage max. 12 VAC/DC connection
in the left-hand terminal compartment!
Terminal:
Connection for:
S1 (2x)
Sensor 1 collector
S2 (2x)
Sensor 2 storage tank low
S3 (2x)
Sensor 3 storage tank top
The polarity of the sensors is freely selectable.
Mains voltages 230 VAC 50-60 Hz Connection
in the right-hand terminal compartment!
Terminal:
Connection for:
L
Mains phase conductor L
N
Mains neutral conductor N
R1
Pump L (speed)
N
Pump N
R2
Zone valve L
N
Zone valve N
The PE protective conductor must be connected
to the PE metal terminal block!
Sensor side
max. 12 V
Mains side
230 VAC
Relay R1: For speed control of
standard pumps, minimum load 20 VA
Low voltage max. 12 VAC/DC connection
in the left-hand terminal compartment!
Terminal:
Connection for:
S1 (2x)
Sensor 1 collector
S2 (2x)
Sensor 2 storage tank
S3 (2x)
Sensor 3 forward flow
The polarity of the sensors is freely selectable.
Mains voltages 230 VAC 50-60 Hz Connection
in the right-hand terminal compartment!
Terminal:
Connection for:
L
Mains phase conductor L
N
Mains neutral conductor N
R1
Pump, secondary L (speed)
N
Pump, secondary N
R2
Pump, primary L
N
Pump, primary N
The PE protective conductor must be connected
to the PE metal terminal block!
Caution
Caution