Temperature Difference Controller TDC 3
Page 20 of 47
D.19 Universal
∆
T controller
Brief description of switching function:
The
∆
T function sensor 1 > sensor 2
switches the pump to relay R1.
The thermostat function via sensor 3
switches the pump to relay R2.
D.20 Universal 2x
∆
T-controller
Brief description of switching function:
The
∆
T function sensor 1 > sensor 2
switches the pump to relay R1.
The
∆
T function 2 > sensor 3
switches the pump to relay R2.
Sensor side
max. 12 V
Mains side
230 VAC
Relay R1: For speed control of
standard pumps, minimum load 20 VA
Caution
Low voltage max. 12 VAC/DC connection
in the left-hand terminal compartment!
Terminal:
Connection for:
S1 (2x)
Sensor 1 (control)
S2 (2x)
Sensor 2 (reference)
S3 (2x)
Sensor 3 (thermostat)
The polarity of the sensors is freely selectable.
Mains voltages 230 VAC 50-60 Hz Connection
in the right-hand terminal compartment!
Terminal:
Connection for:
L
Mains phase conductor L
N
Mains neutral conductor N
R1
Pump L (speed)
N
Pump N
R2
e.g. pump L
N
e.g. pump N
The PE protective conductor must be
connected to the PE metal terminal block!
Sensor side
max. 12 V
Mains side
230 VAC
Relay R1: For speed control of
standard pumps, minimum load 20 VA
Caution
Low voltage max. 12 VAC/DC connection
in the left-hand terminal compartment!
Terminal:
Connection for:
S1 (2x)
Sensor 1 (control)
S2 (2x)
Sensor 2 (ref.+contr.)
S3 (2x)
Sensor 3 (reference)
The polarity of the sensors is freely selectable.
Mains voltages 230 VAC 50-60 Hz Connection
in the right-hand terminal compartment!
Terminal:
Connection for:
L
Mains phase conductor L
N
Mains neutral conductor N
R1
Pump L (speed)
N
Pump N
R2
e.g. pump L
N
e.g. pump N
The PE protective conductor must be
connected to the PE metal terminal block!