07/2015
Temperature Difference Controller TDC 3
Page 28 of 47
5. Settings
5.1 Tmin S1
Enable/start temperature at sensor 1
If this value is exceeded at sensor 1 and the other conditions are also met, then the controller
switches the associated pump and/or valve on. If the temperature at sensor 1 drops below this
value by 5°C, then the pump and/or the valve are switched off again.
Setting range: from 0 °C to 99 °C/default setting: 20 °C
5.2 Tmin S2
Enable/start temperature at sensor 2
If this value is exceeded at sensor 2 and the other conditions are also met, then the controller
switches the associated pump and/or valve on. If the temperature at sensor 2 drops below this
value by 5°C, then the pump and/or the valve are switched off again.
Setting range: from 0 °C to 99 °C/default setting: 40 °C
5.3 Tmin S3
Enable/start temperature at sensor 3
If this value is exceeded at sensor 3 and the other conditions are also met, then the controller
switches the associated pump and/or valve on. If the temperature at sensor 3 drops below this
value by 5°C, then the pump and/or the valve are switched off again.
Setting range: from 0 °C to 99 °C/default setting: 20 °C
The necessary basic settings required for the control
function are made in menu “5. Settings”.
The menu is closed by pressing “esc” or selecting
“Exit settings”.
This does not under any circumstances
replace the safety facilities to be provided
by the customer!
Caution
Caution
Various settings can be made depending on the selection of hydraulic variant
1-20. This is explained in more detail in Table 5.17. This table also indicates the
associated reference sensors and switch outputs. The following pages contain
generally valid descriptions for the settings.