07/2015
Temperature Difference Controller TDC 3
Page 35 of 47
6.3 System protection
Priority protection
System protection prevents overheating of system components by automatic shutdown of the
solar pump. If “SProt Ton” is exceeded at the collector, the pump is switched off. The pump is
activated again when the temperature drops below “SProt TOff”.
Automatic shutdown - settings range: On / Off / Default: on
SProt Ton - settings range: 60 °C to 150 °C / Default: 120 °C
SProt Toff - settings range: 50 °C to Ton minus 5 °C / Default: 115 °C
6.4 Collector protection
Collector protection prevents overheating of the collector. The pump is switched on to transfer
heat from the collector to the storage tank. If “CP Ton” is exceeded at the collector sensor, the
pump is switched on until the temperature reaches “CP Toff” or the temperature “CP Tmax
storage” is exceeded in the storage or pool.
Collector protection settings range: on / off / Default: off
CP Ton settings range: 60 °C to 150 °C / Default: 110 °C
CP Toff settings range: 50 °C to Ton minus 5 °C / Default: 100 °C
CP Tmax storage settings range: 0 °C to 140 °C / Default: 90 °C
Caution
When system protection is on, the temperature in the idle collector will be very
high, thus the pressure in the system will rise and can damage your system.
Pay close attention to the instructions of the system manufacturer.
Danger
When collector protection is active, the storage or pool is heated well
beyond Tmax S2 (see 5.2) which can result in scalding and system damage.