7. Special functions
7.1 Program selections
The suitable hydraulic variant for the specific application is selected and set here (see B.5
Hydraulic variants). The associated diagram can be displayed by pressing “info”.
Setting range: 1-15/default setting: 1
7.2 Time & date
This menu is used to set the current time and date.
7.3 Sensor calibration
Deviations in the temperature values displayed, for example due to cables which are to long or
sensors which are not positioned optimally, can be compensated for manually here.
The settings can be made for each individual sensor in steps of 0.5 °C.
Offset S1...S3 per setting range: -100 to +100 (translates to -50 °C...+50 °C)
Default setting: 0
Menu “7. Special functions” is used to set basic
items and expanded functions.
The menu is closed by pressing “esc” or selecting
“Exit special functions”.
Caution
Other than the time all settings may
only be made by a specialist.
Caution
Normally the program selection is made only once during initial commissioning by
the specialist. Incorrect program selection can lead to unpredictable errors.
Caution
For analysis of the system data it is essential for the time to be set accurately
on the controller. Please note that the clock does not continue to run if the
mains voltage is interrupted, and must therefore be reset.
Caution
Settings are only necessary in special cases at the time of initial
commissioning by the specialist. Incorrect measurement values can lead to
unpredictable errors.