07/2015
Temperature Difference Controller TDC 3
Page 42 of 47
7.9.2 Purging time
During this time the pump starts up at its full speed (100 %) to ensure reliable starting. Only after
this purging time does the pump run with speed control and switches to the max. or min. speed,
depending on the variant set.
Setting range: from 5 to 600 seconds/default setting: 8 seconds
7.9.3 Sweep time
The control time is used to determine the delay for speed control in order to avoid large
temperature oscillations as much as possible. The time span required for a complete control
process from minimum speed to maximum speed is entered here.
Setting range: from 1 to 15 minutes/default setting: 4 minutes
7.9.4 Max. speed
The maximum speed of the pump at relay R1 is specified here. During the setting the pump runs
at the specified speed and the flow rate can be determined.
Setting range: from 70 to 100 %/default setting: 100 %
7.9.5 Min. speed
The minimum speed of the pump at relay R1 is specified here. During the setting the pump runs at
the specified speed and the flow rate can be determined.
Setting range: from 30 to max. speed – 5 %/default setting: 50 %
7.9.6 Setpoint
This value is the control setpoint for variant 3. If the value at the collector sensor drops below this,
the speed is reduced. If it rises above this, the speed is increased.
Setting range: from 0 to 90 °C/default setting: 60 °C
Caution
The indicated percentages are guide values that may vary to a greater or
lesser extent depending on the system, pump and pump stage.
Caution
The indicated percentages are guide values that may vary to a greater or
lesser extent depending on the system, pump and pump stage.