07/2015
Temperature Difference Controller TDC 3
Page 46 of 47
Z.2 Replacing the fuse
Z.3 Maintenance
Performing maintenance:
- Check the date and time (see 7.2)
- Assess/check plausibility of analyses (see 2.4)
- Check the error memory (see 2.5)
- Verify/check plausibility of the current measurement values (see 1.)
- Check the switch outputs/consumers in manual mode (see 4.2)
- Poss. optimize the parameter settings
Danger
Repairs and maintenance may only be performed by a specialist. Before working
on the unit, switch off the power supply and secure it against being switched on
again! Check for the absence of power!
Danger
Only use the supplied spare fuse or a fuse of the same design with the
following specifi cations: T2A 250 V
Z.2.1
If the mains voltage is switched on and the
controller still does not function or display
anything, then the internal device fuse may
be defective. In that case, open
the device as described under C, remove
the old fuse and check it.
Exchange the defective fuse for a new one,
locate the external source of the error (e.g.
pump) and exchange it. Then first
recommission the controller and
check the function of the switch outputs in
manual mode as described under 4.2.
Caution
In the course of the general annual maintenance of your heating system
you should also have the functions of the controller checked by a specialist
and have the settings optimized if necessary.